Attachment J – Altered Facilities

 

 

1.         Within 3 years of the effective date of the Agreement, the City will complete the following modifications to the Police Administration Building, located at 1710 1st Ave., Birmingham, Alabama:

 

a.         Exterior Entrance and Doors.  The exterior entrance door is inaccessible because there is a slope of 6.6% within the door’s required maneuvering clearance.  Provide a door so that the floor or ground area within the required clearances is level and clear.  Standards §§ 4.1.3(7)(a), 4.1.6(1)(b), 4.13.6, Fig. 25.

 

b.         Signage.  The permanent room number signs lack raised and Braille characters.  Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door.  Standards §§ 4.1.2(7), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

 

c.         Alarms.  Although the facility contains an emergency alarm system, the alarm system is inaccessible because the 6th floor conference room lacks a visual alarm.  Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use.  Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate.  Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower.  Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal.  In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling.  Standards §§ 4.1.3(14), 4.1.6(1)(b), 4.28.3.

 

d.         1st Floor Main Lobby Service Counter.  The service counter is inaccessible because it is mounted 41 inches above the finished floor.  Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation.   Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means.  Standards §§ 4.1.1(2), 4.1.6(1)(b), 7.2(2), 4.1.3(1), 4.3.

 

e.         1st Floor Public Service Office.  The service counter is inaccessible because it is mounted 37 inches above the finished floor.  Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation.  Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means.  Standards §§ 4.1.1(2), 4.1.6(1)(b), 7.2(2), 4.1.3(1), 4.3.

 

f.          6th Floor Chief Reception.  The service counter is inaccessible because it is mounted 44 inches above the finished floor.  Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation.  Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means.  Standards §§ 4.1.1(2), 4.1.6(1)(b), 7.2(2), 4.1.3(1), 4.3.

 

g.         Museum Room 102.  The museum room door is inaccessible because the pressure required to open the door is more than 5 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

h.         Elevator

(1)       The elevator is inaccessible because the elevator door closes 3 seconds after re-opening in response to an obstruction.  Provide doors that open and close automatically with a reopening device that will stop and reopen the car door and hoistway door automatically if the door becomes obstructed by an object or person.  Ensure that the device is capable of completing these operations without requiring contact for obstructions passing through the opening at heights of 5 inches and 29 inches above the finished floor; that door reopening devices remain effective for at least 20 seconds, after which the doors may close; that the minimum time from notification that a car is answering a call until the doors of that car start to close is 5 seconds; and that the minimum time for elevator doors to remain fully open in response to a car call is 3 seconds.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.6, 4.10.7, 4.10.8, Figs. 20, 21.

(2)       The elevator is inaccessible because, although emergency communications are provided, they are not identified by raised symbols and lettering, the door to the emergency communications panel requires tight grasping, pinching, or twisting of the wrist and the emergency communications system does not operate without voice communication.  Provide a two-way communication system such that it does not require voice communication, the highest operable part is a maximum of 48 inches above the finished floor of the car, and it is identified by a raised symbol and lettering located adjacent to the device.  If the system uses a handset, ensure that the length of the cord from the panel to the handset is at least 29 inches.  If the system is located in a closed compartment, ensure that the compartment door hardware operates without tight grasping, pinching or twisting of the wrist.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.14.

 

i.          Unisex Single User Toilet Room–Right of Public Service

(1)       The toilet room lacks accessible signage.  Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

(2)       The toilet room door is inaccessible because the pressure required to open the door is more than 5 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

(3)       No accessible coat hook has been provided.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

(4)       No accessible mirror has been provided.  Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.

(5)       The overall length of the rear grab bar is 31 inches, the far end of the rear grab bar is mounted 34 inches from the rear wall, and the rear grab bar is mounted 37 inches above the finished floor.  Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, 4.26.2, Fig. 30.

 

j.          Unisex Single User Toilet Room– Left of Public Service

(1)       The toilet room door lacks accessible signage.  Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

(2)       The toilet room door is inaccessible because the pressure required to open the door is more than 5 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

(3)       No accessible coat hook has been provided.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

(4)       No accessible mirror has been provided.  Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.

(5)       The overall length of the rear grab bar is 30 inches.  Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Fig. 30.

(6)       The far end of the side grab bar is mounted 34½ inches from the rear wall.  Provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29(b).

 

k.         3rd Floor Women’s Toilet Room with Stalls

(1)       The toilet room door is inaccessible because the pressure required to open the door is more than 5 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

(2)       No accessible mirror has been provided.  Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.

(3)       The paper towel dispenser is inaccessible because the controls are mounted 55 inches above the finished floor.  Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

(4)       No accessible coat hook has been provided in the accessible stall.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

l.          3rd Floor Men’s Toilet Room with Stalls

(1)       The toilet room door is inaccessible because the pressure required to open the door is more than 5 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

(2)       No accessible mirror has been provided.  Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.

(3)       The paper towel dispenser is inaccessible because the controls are mounted 55½ inches above the finished floor.  Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

(4)       The route to the urinal narrows to approximately 28 inches at the pilaster that supports the privacy screen.  Provide an accessible route to the urinal with a minimum clear width of 36 inches, except at doors, where the width may decrease to 32 inches.  Standards §§ 4.1.3(1), 4.1.6(1)(b), 4.3.3, 4.13.5.

 

m.        1st Floor Women’s Toilet Room with Stalls

(1)       The toilet room door is inaccessible because the pressure required to open the door is more than 5 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

(2)       The toilet room door lacks adequate space on the latch side of the door on the pull side, due to a piece of removable furniture.  On the pull side of the door, provide and maintain a path of travel at least 48 inches wide for a side approach and at least 24 inches of clear maneuvering space adjacent to the latch side of the door.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(c).

(3)       The paper towel dispenser is inaccessible because the controls are mounted 56 inches above the finished floor.  Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

(4)       The toilet centerline in the accessible stall is 20 inches from the side wall.  Provide a toilet with a centerline that measures 18 inches from the near side wall.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30.

(5)       The far end of the side grab bar is mounted 50 inches from the rear wall.  Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as the toilet paper dispenser.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, 4.26.2, Figs. 30(a), (d).

 

n.         1st Floor Men’s Toilet Room

(1)       The toilet room door is inaccessible because the pressure required to open the door is more than 5 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

(2)       The toilet seat cover dispenser is inaccessible because it is mounted 56 inches above the finished floor.  Provide a toilet seat cover dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6, Fig. 4.

(3)       The toilet centerline in the accessible stall is 20½ inches from the side wall.  Provide a toilet with a centerline that measures 18 inches from the near side wall.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30.

(4)       The far end of the side grab bar is mounted 50 inches from the rear wall.  Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as the toilet paper dispenser.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, 4.26.2, Figs. 30(a), (d).

 

o.         6th Floor Women’s Toilet Room with Stalls

(1)       The toilet room door is inaccessible because the pressure required to open the door is more than 5 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

(2)       No accessible mirror has been provided.  Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.

(3)       The paper towel dispenser is inaccessible because the controls are mounted 56 inches above the finished floor.  Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

(4)       The overall length of the rear grab bar is 30 inches.  Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Fig. 30.

 

p.         6th Floor Men’s Toilet Room with Stalls

(1)       The toilet room door is inaccessible because the pressure required to open the door is more than 5 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

(2)       No accessible mirror has been provided.  Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.

(3)       The paper towel dispenser is inaccessible because the controls are mounted 56 inches above the finished floor.  Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

(4)       There is a counter that protrudes into the path of travel.  Provide an accessible route to the toilet room with required minimum width, passing space, head room, surface textures, slopes, and changes in level.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.1, 4.3.1, 4.3.2, 4.3.3, 4.3.4, 4.3.5, 4.3.6, 4.3.7, 4.3.8.

(5)       The overall length of the rear grab bar is 30 inches.  Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Fig. 30.

 

q.         5th Floor Women’s Toilet Room

(1)       The toilet room door is inaccessible because the pressure required to open the door is more than 5 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

(2)       No accessible mirror has been provided.  Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.

(3)       The overall length of the rear grab bar is 30 inches.  Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Fig. 30.

 

r.          5th Floor Men’s Toilet Room

(1)       The toilet room door is inaccessible because the pressure required to open the door is more than 5 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

(2)       No accessible mirror has been provided.  Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.

(3)       The paper towel dispenser is inaccessible because the controls are mounted 56 inches above the finished floor.  Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

(4)       The overall length of the rear grab bar is 30 inches.  Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Fig. 30.

 

s.         High Public Service Fountain:  The hi-lo drinking fountain is inaccessible because the high fountain is not detectable to a blind person using a cane.  Provide a high drinking fountain at this location such that its bottom leading edges measure no more than 27 inches above the finished floor or protrude no more than 4 inches into the walkway.  Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

 

t.          Basement Fountain:  The low fountain was out of order at the time of the Department’s onsite inspection.  Provide at least one drinking fountain on this floor with a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet; and a spout located at the front of the unit that directs the water flow in a trajectory that is nearly parallel to the front of the unit and is positioned so the flow of water is within 3 inches of the front edge of the fountain and at least 4 inches high.  Ensure that fountain controls are operable with one hand, require 5 lbf or less to operate without tight grasping, pinching, or twisting of the wrist; and are front mounted or side mounted near the front edge.  Standards §§ 4.1.3(10), 4.1.6(1)(b), 4.15, 4.27.4, Fig. 27.

 

 

2.         Within 1 year of the effective date of the Agreement, the City will complete the following modifications to the Museum of Art, located at 2000 8th Ave., Birmingham, Alabama:

 

a.         Parking.  The van accessible parking reserved for persons with disabilities lacks the appropriate signage.  At van accessible spaces, provide a “Van-Accessible” sign located below the International Symbol of Accessibility such that the sign cannot be obstructed by vehicles parked in the space.  Standards §§ 4.1.2(5), 4.1.6(1)(b), 4.6.4, 4.30.7(1).

 

b.         Lobby Area.  There is no accessible telephone in the lobby area.  Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; that is hearing aid compatible and has a volume control mechanism; with telephone books, if provided, located between 15 and 48 inches above the finished floor for a front approach or between 9 and 54 inches above the finished floor for a side approach; with a cord of at least 29 inches long from the telephone to the handset; and with signage that complies with the Standards.  Standards §§ 4.1.3(17), 4.1.6(1)(b), 4.31, 4.30.7(2).

 

c.         Department of Education and Public Programs

(1)       The office door is inaccessible because the pressure required to open the door is more than 5 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

(2)       The office door lacks adequate space and depth on the latch side of the door on the pull side.  On the pull side of the door, provide a path of travel at least 48 inches wide for a side approach and at least 24 inches of clear maneuvering space adjacent to the latch side of the door.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(c).

(3)       The service counter is inaccessible because it is mounted 44 inches above the finished floor.  Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation.   Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means.  Standards §§ 4.1.1(2), 4.1.6(1)(b), 7.2(2), 4.1.3(1), 4.3.

 

d.         1st Curatorial Drinking Fountain.  The drinking fountain controls require 7 pounds of force to operate.  Provide a drinking fountain with controls mounted on or near the front edge that are operable with one hand, that require 5 lbf or less to operate, and that can be operated without tight grasping, pinching, or twisting of the wrist.  Standards §§ 4.1.3(10), 4.1.6(1)(b), 4.15.4, 4.27.4.

 

e.         Lobby Area Men’s Toilet Room with Stalls

(1)       The toilet room sign is mounted 62 inches above the finished floor.  Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

(2)       The toilet room door is inaccessible because the pressure required to open the door is 16 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

(3)       Although the facility contains an emergency alarm system, the alarm system is inaccessible because the toilet room lacks a visual alarm.  Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use.  Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate.  Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower.  Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal.  In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling.  Standards §§ 4.1.3(14), 4.1.6(1)(b), 4.28.3.

 

f.          Lobby Area Women’s Toilet Room with Stalls

(1)       The toilet room door is inaccessible because the pressure required to open the door is 15 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

(2)       Although the facility contains an emergency alarm system, the alarm system is inaccessible because the toilet room lacks a visual alarm.  Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use.  Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate.  Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower.  Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal.  In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling.  Standards §§ 4.1.3(14), 4.1.6(1)(b), 4.28.3.

(3)       The toilet paper dispenser in the designated accessible stall is mounted 16 inches above the finished floor.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

(4)       The toilet paper dispenser in the alternate stall is mounted 16 inches above the finished floor.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

 

g.         Curatorial Women’s Toilet Room with Stalls

(1)       The toilet room sign is mounted on the door.  Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

(2)       The toilet room door is inaccessible because the pressure required to open the door is 11 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

(3)       Although the facility contains an emergency alarm system, the alarm system is inaccessible because the toilet room lacks a visual alarm.  Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use.  Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate.  Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower.  Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal.  In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling.  Standards §§ 4.1.3(14), 4.1.6(1)(b), 4.28.3.

(4)       The toilet paper dispenser in the accessible stall is mounted 15 inches above the finished floor.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

 

h.         Curatorial Men’s Toilet Room with Stalls

(1)       The toilet room sign is mounted on the door.  Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

(2)       The toilet room door is inaccessible because the pressure required to open the door is 12 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

(3)       Although the facility contains an emergency alarm system, the alarm system is inaccessible because the toilet room lacks a visual alarm.  Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use.  Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate.  Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower.  Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal.  In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling.  Standards §§ 4.1.3(14), 4.1.6(1)(b), 4.28.3.

(4)       The urinal rim is mounted 20½  inches above the finished floor.  Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.5, 4.18.2, 4.18.3, 4.18.4.

(5)       The toilet paper dispenser in the accessible stall is mounted 15 inches above the finished floor.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

 

i.          Lobby Single User Toilet Room

(1)       The toilet room door lacks accessible signage.  Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

(2)       The toilet room door is inaccessible because the pressure required to open the door is 15 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

(3)       Although the facility contains an emergency alarm system, the alarm system is inaccessible because the toilet room lacks a visual alarm.  Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use.  Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate.  Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower.  Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal.  In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling.  Standards §§ 4.1.3(14), 4.1.6(1)(b), 4.28.3.

(4)       No accessible mirror has been provided.  Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.

(5)       The toilet paper dispenser is mounted 16 inches above the finished floor.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

(6)       No accessible coat hook has been provided.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

j.          West Lobby 2nd Floor Men’s Toilet Room with Stalls

(1)       The toilet room signage is inaccessible.  Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

(2)       Although the facility contains an emergency alarm system, the alarm system is inaccessible because the toilet room lacks a visual alarm.  Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use.  Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate.  Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower.  Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal.  In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling.  Standards §§ 4.1.3(14), 4.1.6(1)(b), 4.28.3.

(3)       The urinal lacks the required clear floor space.  Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.5, 4.18.2, 4.18.3, 4.18.4.

(4)       The accessible stall door is inaccessible because knob hardware is used.  Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate.  Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.9.

(5)       The toilet paper dispenser in the accessible stall is mounted 16 inches above the finished floor.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

 

k.         West Lobby 2nd Floor Women’s Toilet Room with Stalls

(1)       The toilet room signage is inaccessible.  Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

(2)       Although the facility contains an emergency alarm system, the alarm system is inaccessible because the toilet room lacks a visual alarm.  Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use.  Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate.  Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower.  Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal.  In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling.  Standards §§ 4.1.3(14), 4.1.6(1)(b), 4.28.3.

(3)       The toilet paper dispenser in the accessible stall is mounted 15 inches above the finished floor.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

 

l.          East Side 3rd Floor Women’s Toilet Room with Stalls

(1)       The toilet room signage is inaccessible.  Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

(2)       The toilet room door is inaccessible because the pressure required to open the door is 10 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

(3)       Although the facility contains an emergency alarm system, the alarm system is inaccessible because the toilet room lacks a visual alarm.  Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use.  Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate.  Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower.  Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal.  In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling.  Standards §§ 4.1.3(14), 4.1.6(1)(b), 4.28.3.

(4)       The toilet paper dispenser in the accessible stall is mounted 15 inches above the finished floor.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

 

m.        East Side 3rd Floor Men’s Toilet Room with Stalls

(1)       The toilet room signage is inaccessible.  Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

(2)       The toilet room door is inaccessible because the pressure required to open the door is 10 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

(3)       Although the facility contains an emergency alarm system, the alarm system is inaccessible because the toilet room lacks a visual alarm.  Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use.  Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate.  Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower.  Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal.  In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling.  Standards §§ 4.1.3(14), 4.1.6(1)(b), 4.28.3.

(4)       The toilet paper dispenser in the accessible stall is mounted 15 inches above the finished floor.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

 

n.         Steiner Auditorium.  The pressure required to open the entrance door is 10 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

o.         Library.  The counter is inaccessible because its top surface is 42 inches above the finished floor.  Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation.   Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means.  Standards §§ 4.1.1(2), 4.1.6(1)(b), 7.2(2), 4.1.3(1), 4.3.

 

p.         Elevator (East side).  The elevator is inaccessible because no audible signal is provided as the car passes or stops at a floor served by the elevator.  Provide visual car position indicators above the car control panel or over the door to show the position of the elevator in the hoistway.  Ensure that indicators emit an audible and visual signal as the car passes or stops at a floor served by the elevator, with the corresponding floor designation being illuminated; and that numerals are a minimum of ½ inch high.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.13.

 

3.         Within 2 years of the effective date of the Agreement, the City will complete the following modifications to the  Birmingham Botanical Gardens, located at 3324 Lane Park Drive, Birmingham, Alabama:

 

a.         Education Building:

 

(1)       Visual Alarms Are Missing in Multiple Rooms:  Although audible alarms are provided, there are no visual alarms in the second floor conference/ board room; the second floor break room; the East Room; the Ireland Room; the men’s and women’s toilet rooms near the East Room; the men’s and women’s toilet rooms serving the Café de France; and other common use areas.  Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use.  Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate.  Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower.  Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal.  In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling.  Standards §§ 4.1.3(14), 4.1.6(1)(b), 4.28.3.

 

(2)       Single-User Toilet Rooms Serving Café de France

(a)       The entrance to both  toilet room doors is inaccessible because the pressure required to open the door is more than 5 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

(b)       No accessible mirror has been provided.  Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.

(c)       The soap dispenser is mounted too high.  Provide a soap dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

 

(3)       Women’s 2nd Floor South Toilet Room with Stalls

(a)       No accessible coat hook has been provided.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

(4)       Toilet Rooms with Stalls Near Plant Information Office

(a)       No accessible coat hook has been provided in both designated accessible stalls.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

(b)       The toilet room doors are inaccessible because the pressure required to open the door is more than 5 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

(c)       The hot water pipes on the lavatory in each room are not insulated or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.4.

(d)       The flush control on the toilet in the women’s toilet room is on the closed side.  Provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.17.2, 4.27.4.

(e)       The toilet paper dispenser in the men’s toilet room is mounted too far from the rear wall.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

 

(5)       Toilet Rooms with Stalls Near Hodges Room

(a)       In each, for the toilet stall designed for ambulatory people with disabilities, the door is not self-closing and the stall is too wide.  Provide at least one stall that is exactly 36 inches wide with an outward swinging, self-closing door and parallel grab bars complying with Fig 30(d).  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, Fig. 30(d). 

(b)       No accessible coat hook has been provided in both the men’s and women’s toilet rooms.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

(6)       Library.  The check-out area is inaccessible because the counter is mounted 44 inches above the finished floor.  Provide at least one accessible lane at each check out area such that the counter is on an accessible route at least 36 inches wide and it has a section at least 36 inches wide and no more than 36 inches above the finished floor.  Standards §§ 4.1.6(1)(b), 8.3, 7.2(1).

 

(7)       Linn-Henley Lecture Hall

(a)       The lecture hall lacks wheelchair seating areas.  Provide wheelchair seating areas as required by Standards § 4.1.3(19)(a), each with a minimum clear ground or floor space of 66 inches wide by 48 inches deep for forward or rear access, or 66 inches wide by 60 inches deep for side access.  Ensure that the ground or floor at all wheelchair locations is level, firm, stable, and slip resistant; that wheelchair seating areas are an integral part of the fixed seating plan and are located so as to provide people with physical disabilities a choice of lines of sight comparable to those available for members of the general public; that wheelchair seating areas adjoin an accessible route that also serves as a means of egress in case of emergency; and that at least one fixed companion seat is provided next to each wheelchair seating area.  Standards §§ 4.1.3(19)(a), 4.1.6(1)(b), 4.5, 4.33.

(b)       The top run of the existing ramp from the spectator seating to the stage is too steep and there is insufficient maneuvering clearance at the level landing/ change of direction on the ramp.  Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public.  The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%).  Standards §§ 4.1.3(1), 4.1.6(1)(b), 4.3, 4.5, Fig. 7.

 

(8)       Exploration Room Single User Toilet Room

(a)       The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.4.

(b)       No accessible mirror has been provided.  Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.

 

b.         Toilet Room Building Near Japanese Gardens

 

(1)       Men’s and Women’s Toilet Rooms with Stalls

(a)       In each toilet room there is no accessible signage.  Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

(b)       In each toilet room the configuration of the entrance blocks people who use wheelchairs from entering because the path narrows to 35 inches where users must change direction.  Provide an accessible route to the toilet rooms with a minimum clear width of 36 inches, except at doors, where the width may decrease to 32 inches.  Standards §§ 4.1.3(1), 4.1.6(1)(b), 4.3.3, 4.13.5.

(c)       In the women’s toilet stall for persons who use wheelchairs, the toilet paper dispenser is mounted with its center 41 inches from the rear wall.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

(d)       In the women’s toilet stall for persons who use wheelchairs, the stall door hardware requires too much pressure to operate.  Provide door hardware with mechanical controls, if any, that can be operated with 5 lbf or less and that can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs).  Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.4.

(e)       No accessible coat hook has been provided in the men’s toilet room.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.