Attachment J – Altered Facilities


 

1.         Except as otherwise noted, within 6 months of the effective date of the Agreement, the County will complete the following modifications to the Upper Kanawha Valley Enterprise Community (UKVEC), located at 200 Upper Kanawha Valley Way, Cabin Creek.

 

            A.        Women’s Lobby Toilet Room: Single-User

 

                        1)        The signage provided is inaccessible because the sign is not mounted on the latch side of the door, the centerline of the sign is 67 inches above the finished floor, and there are no Braille characters. Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door. Standards §§ 4.1.2(7), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

 

                        2)        The women’s toilet room door is inaccessible because the pressure required to open the door is 8 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

                        3)        No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

                        4)        No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.

 

                        5)        The lavatory is inaccessible because the bottom edge of the apron is 27½ inches high, and the knee and toe clearances do not comply with Fig. 31. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, Fig. 31.

 

                        6)        The toilet is inaccessible because its centerline measures 17 inches from the side wall. Within 18 months of the effective date of this Agreement, provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.2, Fig. 28.

 

                        7)        The toilet is inaccessible because the flush control is on the closed side. Provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.27.4.

 

                        8)        The side grab bar at the toilet is inaccessible because the far end of the bar is 49 inches from the rear wall. Provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29(b).

 

                        9)        The rear grab bar at the toilet is inaccessible because it is obstructed by the toilet seat cover dispenser. Provide a rear grab bar that has at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, 4.26.2, Fig. 39.

 

            B.        Men’s Lobby Toilet Room: Single-User

 

                        1)        The signage provided is inaccessible because the sign is not mounted on the latch side of the door, the centerline of the sign is 67 inches above the finished floor, and there are no Braille characters. Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door. Standards §§ 4.1.2(7), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

 

                        2)        The men’s toilet room door is inaccessible because the pressure required to open the door is 7 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

                        3)        No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

                        4)        No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.

 

                        5)        The paper towel dispenser is inaccessible because it is mounted too high. Provide a towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

 

                        6)        The lavatory is inaccessible because the bottom edge of the apron is 27½ inches high, and the knee and toe clearances do not comply with Fig. 31 because the basin is in the way. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, Fig. 31.

 

                        7)        The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.4.

 

                        8)        The side grab bar at the toilet is inaccessible because the far end of the bar is 49½ inches from the rear wall. Provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29(b).

 

                        9)        The shelf under the mirror protrudes into the walkway and would not be detectable to a blind person using a cane. Provide a circulation path at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

 

            C.        Tincher Safety, Inc. – Lobby

 

                        1)        The office door is inaccessible because the pressure required to open the door is 10 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

            D.        Men’s First Floor Toilet Room- not altered

 

                        1)        The signage provided is inaccessible because the sign is not mounted on the latch side of the door, and there are no Braille characters. Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door. Standards §§ 4.1.2(7), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

 

                        2)        There is no signage directing people with disabilities to the accessible toilet rooms. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible toilet rooms indicating the location of the nearest accessible toilet room, and provide accessible signage with the International Symbol of Accessibility at all accessible toilet rooms. Standards §§ 4.1.2(7)(d), 4.1.6(3)(e)(iii), 4.30.1, 4.30.2, 4.30.3, 4.30.5, 4.30.7.

 

                        3)        The men’s toilet room door is inaccessible because the pressure required to open the door is 8 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

                        4)        No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.

 

                        5)        The paper towel dispenser is inaccessible because the controls are mounted at 48 inches above the finished floor and it requires a forward approach. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

 

                        6)        The lavatory is inaccessible because the pipes interfere with knee and toe clearances. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, Fig. 31.

 

            E.        Women’s First Floor Toilet Room- not altered

 

                        1)        There is no signage directing people with disabilities to the accessible toilet rooms. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible toilet rooms indicating the location of the nearest accessible toilet room, and provide accessible signage with the International Symbol of Accessibility at all accessible toilet rooms. Standards §§ 4.1.2(7)(d), 4.1.6(3)(e)(iii), 4.30.1, 4.30.2, 4.30.3, 4.30.5, 4.30.7.

 

                        2)        The women’s toilet room door is inaccessible because the pressure required to open the door is 6 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

                        3)        No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.

 

                        4)        The lavatory is inaccessible because the pipes prevent adequate knee and toe clearance. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, Fig. 31.

 

            F.        Sheriff’s Department – First Floor

 

                        1)        The door to the Sheriff’s Department is inaccessible because there is a 1½ inch threshold. Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.8, 4.5.2.

 

            G.        Curves For Women – First Floor

 

                        1)        The door to Curves for Women is inaccessible because the threshold is greater than ½ inch high and not beveled. Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.8, 4.5.2.

 

            H.        Women’s Second Floor Toilet Room with Stalls

 

                        1)        The toilet room sign is inaccessible since it is mounted on the door and has a centerline of 64½ inches high. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

 

                        2)        The soap dispenser is inaccessible because the controls are mounted at 52½ inches above the finished floor and require a forward approach. Provide a soap dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

 

                        3)        The paper towel dispenser is inaccessible because the controls are mounted at 60½ inches above the finished floor and require a forward reach. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

 

                        4)        The lavatory is inaccessible because the sink bowl prevents adequate knee and toe clearances. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, Fig. 31.

 

                        5)        The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.4.

 

                        6)        The toilet is inaccessible because its centerline measures 19 inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30.

 

                        7)        The coat hook is mounted at 66½ inches. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

                        8)        The toilet paper dispenser is inaccessible because it is mounted too far from the rear wall. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

 

                        9)        There are no grab bars provided at the toilet. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall, and a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Ensure that the grab bars are mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any object beside or below it and at least 18 inches between the grab bar and any object above it. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, 4.26.2, Figs. 30, 39.

 

            I.         Men’s Second Floor Toilet Room with Stalls

 

                        1)        The toilet room sign is inaccessible because it is mounted on the door and has a centerline 64 inches high. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

 

                        2)        The door to the men’s toilet room, which is accessed from the latch side of the door, is inaccessible because it has inadequate maneuvering clearance. On the pull side of the door, provide a path of travel at least 48 inches wide for a side approach and at least 24 inches of clear maneuvering space adjacent to the latch side of the door. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(c).

 

                        3)        The soap dispenser is inaccessible because the controls are mounted at 51 inches above the finished floor and require a forward reach. Provide a soap dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

 

                        4)        The paper towel dispenser is inaccessible because the controls are mounted at 63 inches above the finished floor and require a forward reach. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

 

                        5)        The lavatory is inaccessible because the sink bowl creates inadequate knee and toe clearances. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, Fig. 31.

 

                        6)        The toilet is inaccessible because its centerline measures 19 inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30.

 

                        7)        The toilet is inaccessible because the flush control is mounted on the closed side. Provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.17.2, 4.27.4.

 

                        8)        The coat hook is mounted at 66½ inches. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

                        9)        The toilet paper dispenser is inaccessible because it is mounted 40 inches from the rear wall. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

 

                        10)      The toilet is inaccessible because no grab bars have been provided. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall, and a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Ensure that the grab bars are mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any object beside or below it and at least 18 inches between the grab bar and any object above it. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, 4.26.2, Figs. 30, 39.

 

            J.         Parking

 

                        1)        Although the parking lot has a total of 81 parking spaces, an inadequate number are designated as reserved for people with disabilities. On the shortest accessible route to the accessible entrance, provide 1 van accessible space and 4 standard spaces designated as reserved for people with disabilities. Standard accessible spaces shall be a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Van accessible spaces shall be a minimum of 96 inches wide and served by access aisles at least 96 inches wide. All spaces designated as reserved for people with disabilities shall have vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. Van accessible spaces shall have an additional “Van-Accessible” sign located below the International Symbol of Accessibility. Standards §§ 4.1.2(5), 4.1.6(1)(b), 4.6, 4.30.7(1).

 

                        2)        The parking lot is inaccessible because there are no access aisles. At each standard accessible space, provide an access aisle at least 60 inches wide. At each van accessible space, provide an access aisles at least 96 inches wide. Ensure that all access aisles are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.1.6(1)(b), 4.6.3, Fig. 9.

 

            K.        Exterior Entrance and Doors

 

                        1)        The interior door at the main entrance is inaccessible because the pressure required to open the door is 16 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

            L.        Platform Lift

 

                        1)        The platform lift requires a key to call the lift and to operate the lift from inside. There is no key on the outside of the lift at the top or the bottom. As a result, if the lift is on the upper level, it cannot be called down to the lower level without a key. In addition, the key requires twisting to operate. Finally, the call button must remain pressed for the lift to operate. Provide a platform lift that facilitates unassisted entry, operation, and exit from the lift. Standards §§ 4.11.2, 4.11.3, 4.27.4.

 

2.         Except as otherwise noted, within 12 months of the effective date of the Agreement, the County will complete the following modifications to the Judicial Annex, located at 111 Court Street, Charleston.

 

            A.        Interior Signage

 

                        1)        The signage provided throughout the facility is inaccessible because much of it is mounted on the doors and does not contain Braille characters. Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door. Standards §§ 4.1.2(7), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

 

            B.        Drinking Fountains

 

                        1)        Throughout the building, the tall drinking fountains protrude into the walkway and would not be detectable to a blind person using a cane. Provide a circulation path at these locations such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

 

            C.        Men’s Toilet Room with Stalls – 7th floor

 

                        1)        The men’s toilet room door is inaccessible because the pressure required to open the door is 14 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

                        2)        The door to the men’s toilet room, which is accessed through a front approach, is inaccessible because it is obstructed by a plant. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).

 

                        3)        The lavatory is inaccessible because the paper towel dispenser reduces the clear floor space needed to use the fixture. Provide a lavatory with clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.3, Fig. 32.

 

                        4)        The urinal is inaccessible because the rim height is 24 inches. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.5, 4.18.2, 4.18.3, 4.18.4.

 

                        5)        The toilet is inaccessible because its centerline measures 19 inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30.

 

                        6)        No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

                        7)        The side grab bar at the toilet is inaccessible because it is 36 inches long, and the far end of the bar is mounted 42 inches from the rear wall. Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Figs. 30(a), (d).

 

            D.        Women’s Toilet Room with Stalls – 7th floor

 

                        1)        The women’s toilet room door is inaccessible because the pressure required to open the door is 13 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).      

 

                        2)        The lavatory is inaccessible because the paper towel dispenser reduces the clear floor space. Provide a lavatory with clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.3, Fig. 32.

 

                        3)        No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

                        4)        The side grab bar at the toilet is inaccessible because it is 36 inches long, and the far end of the bar is mounted 42 inches from the rear wall. Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Figs. 30(a), (d).

 

                        5)        The side grab bar at the toilet is inaccessible because it is obstructed by the toilet seat cover dispenser. Provide a side grab bar that has at least 1½ inches between the grab bar and any other object, such as the toilet paper dispenser. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, 4.26.2, Fig. 39.

 

            E.        Men’s Toilet Room with Stalls – 6th floor

 

                        1)        The men’s toilet room door is inaccessible because the pressure required to open the door is 13 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

                        2)        The lavatory is inaccessible because the paper towel dispenser reduces the clear floor space. Provide a lavatory with clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.3, Fig. 32.

 

                        3)        The urinal is inaccessible because the rim height is 24½ inches. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.5, 4.18.2, 4.18.3, 4.18.4.

 

                        4)        The toilet is inaccessible because its centerline measures 19 inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30.

 

                        5)        No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

                        6)        The side grab bar at the toilet is inaccessible because it is 36 inches long, and the far end of the bar is mounted 42 inches from the rear wall. Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Figs. 30(a), (d).

 

            F.        Women’s Toilet Room with Stalls – 6th floor

 

                        1)        The door is inaccessible because the pressure required to open the door is 14 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).    

 

                        2)        The lavatory is inaccessible because the paper towel dispenser reduces the clear floor space. Provide a lavatory with clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.3, Fig. 32.

 

                        3)        No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

                        4)        The side grab bar is inaccessible because it is 36 inches long, and the far end of the bar is mounted 42 inches from the rear wall. Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Figs. 30(a), (d).

 

                        5)        The side grab bar at the toilet is inaccessible because it is obstructed by the toilet seat cover dispenser. Provide a side grab bar that has at least 1½ inches between the grab bar and any other object, such as the toilet paper dispenser. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, 4.26.2, Fig. 39

 

            G.        Jury Area 3rd floor: Single User Toilet Room

 

                        1)        The door to the single user toilet room is inaccessible because knob hardware is used. Provide a door with hardware usable with one hand and without tight grasping, pinching, or twisting of the wrist. Lever-operated, push-type, and U-shaped handles are acceptable designs. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.2, 4.13.9.

 

                        2)        The paper towel dispenser is inaccessible because it requires two hands to operate. Provide a paper towel dispenser with mechanical controls, if any, that can be operated with 5 pounds of force or less and that can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.4.

 

                        3)        The toilet is inaccessible because the flush control is on the closed side. Provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.27.4.

 

            H.        Judge Zakaib’s Deliberation Room – 7th floor

 

                        1)        The door to the deliberation room is inaccessible because the pressure required to open the door is 13 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

                        2)        The door to the deliberation room is inaccessible because knob hardware is used. Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.9.

 

                        3)        The door to the deliberation room, which is accessed through a front approach, is inaccessible because it is obstructed by a file cabinet. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).

 

            I.         Jury Deliberation Rooms – 7th floor (Judges Berger, Walker, Bloom, Stucky, and Kaufman)

 

                        1)        The door to the deliberation room is inaccessible because the pressure required to open the door is 13 pounds (Stucky is 15 pounds). Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

                        2)        The door to the deliberation room is inaccessible because knob hardware is used. Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.9.

 

                        3)        The door to the deliberation room, which is accessed through a front approach, is inaccessible because it is obstructed by a moveable coat rack. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).

 

                        4)        No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

            J.         Men’s Toilet Room: Single-User – Berger Courtroom

 

                        1)        The men’s toilet room is inaccessible because knob hardware is used. Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.9.

 

                        2)        No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.

 

                        3)        The toilet is inaccessible because the top of the seat is 15½ inches above the finished floor. Provide a toilet with a seat that measures 17 to 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.3, Fig. 29(b).

 

                        4)        The side grab bar at the toilet is inaccessible because it is 36 inches long and the far end is 43 inches from the rear wall. Provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29(b).

 

                        5)        The rear grab bar at the toilet is inaccessible because it is 30 inches long, and the far end is 34 inches from the side wall. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall and the far end at least 48 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29.

 

                        6)        The rear grab bar at the toilet is inaccessible because the soap dispenser obstructs the clear space above the bar and prevents proper operation. Provide a rear grab bar that has at least 1½ inches between the grab bar and any object beside or below it and at least 18 inches between the grab bar and any object above it. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, 4.26.2, Fig. 39.

 

            K.        Unisex Toilet Room – Berger Courtroom – 7th floor

 

                        1)        The door to the unisex toilet room, which is accessed through a front approach, is inaccessible because it has only 13 inches of maneuvering space. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).

 

                        2)        The door to the unisex toilet room, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 5 inches of maneuvering clearance. On the push side of the door, provide maneuvering clearance at least 48 inches deep and provide a minimum of 12 inches of maneuvering clearance on the latch side of the door, or remove the closer or the latch. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).

 

                        3)        The side grab bar at the toilet is inaccessible because it is 36 inches long and the far end is 43 inches from the rear wall. Provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29(b).

 

                        4)        The side grab bar at the toilet is inaccessible because it is obstructed by the toilet seat cover dispenser. Provide a side grab bar that has at least 1½ inches between the grab bar and any other object, such as the toilet paper dispenser. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, 4.26.2, Fig. 39.

 

                        5)        The rear grab bar at the toilet is inaccessible because it is 30 inches long, and the far end is 34 inches from the side wall. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall and the far end at least 48 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29.

 

            L.        Berger, Bloom, Kaufman, and Zakaib Courtrooms

 

                        1)        The courtroom doors are inaccessible because the pressure required to open each door is 12 pounds. Provide doors that require no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

                        2)        The courtroom has no companion seats provided for the wheelchair seating locations. Provide at least one fixed companion seat next to each wheelchair seating area. Standards §§ 4.1.3(19)(a), 4.1.6(1)(b), 4.5, 4.33, Fig. 46.

 

            M.       Men’s Toilet Room: Single-User – Zakaib – 7th floor

 

                        1)        The men’s toilet room door is inaccessible because knob hardware is used. Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.9.

 

                        2)        No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.

 

                        3)        The toilet is inaccessible because the top of the seat is 15½ inches above the finished floor. Provide a toilet with a seat that measures 17 to 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.3, Fig. 29(b).

 

                        4)        The toilet is inaccessible because its centerline measures 19 inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.2, Fig. 28.

 

                        5)        The side grab bar at the toilet is inaccessible because it is 36 inches long and the far end is mounted 44 inches from the rear wall. Provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29(b).

 

                        6)        The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. Provide a side grab bar that has at least 1½ inches between the grab bar and any other object, such as the toilet paper dispenser. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, 4.26.2, Fig. 39.

 

                        7)        The rear grab bar at the toilet is inaccessible because it is 30 inches long and the far end is 34 inches from the side wall. Provide a rear grab bar that is at least 36 inches in overall length with the far end at least 48 inches from the side wall and the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29.

 

                        8)        The rear grab bar at the toilet is inaccessible because the soap dispenser interferes with the clear space above the bar and prevents access to the bar. Provide a rear grab bar that has at least 1½ inches between the grab bar and any object beside or below it and at least 18 inches between the grab bar and any object above it. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, 4.26.2, Fig. 39.

 

            N.        Unisex Toilet Room: Single-User

 

                        1)        The pull side of the door to the unisex toilet room, which is accessed from the latch side of the door, is inaccessible because it has only 15 inches of maneuvering clearance from the door to the lavatory. On the pull side of the door, provide a path of travel at least 48 inches wide for a side approach and at least 24 inches of clear maneuvering space adjacent to the latch side of the door. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(c).

 

                        2)        The push side of the door to the unisex toilet room, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 6¼ inches of maneuvering clearance. On the push side of the door, provide maneuvering clearance at least 48 inches deep and provide a minimum of 12 inches of maneuvering clearance on the latch side of the door, or remove the closer or the latch. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).

 

                        3)        The side grab bar at the toilet is inaccessible because it is 36 inches long and the far end is mounted 43 inches from the rear wall. Provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29(b).

 

                        4)        The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. Provide a side grab bar that has at least 1½ inches between the grab bar and any other object, such as the toilet paper dispenser. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, 4.26.2, Fig. 39.

 

                        5)        The rear grab bar at the toilet is inaccessible because it is 30 inches long and the far end 34 inches from the side wall. Provide a rear grab bar that is at least 36 inches in overall length with the far end at least 48 inches from the side wall and the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29.

 

                        6)        The rear grab bar at the toilet is inaccessible because the soap dispenser interferes with the clear space above the bar and prevents proper operation. Provide a rear grab bar that has at least 1½ inches between the grab bar and any object beside or below it and at least 18 inches between the grab bar and any object above it. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, 4.26.2, Fig. 39.

 

            O.        Men’s Toilet Room: Single-User – Kaufman Deliberation Room – 6th floor

 

                        1)        The men’s toilet room door is inaccessible because knob hardware is used. Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.9.

 

                        2)        No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.

 

                        3)        The toilet is inaccessible because the top of the seat is 15½ inches above the finished floor. Provide a toilet with a seat that measures 17 to 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.3, Fig. 29(b).

 

                        4)        The toilet is inaccessible because its centerline measures 19 inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.2, Fig. 28.

 

                        5)        The side grab bar at the toilet is inaccessible because it is 36 inches long and the far end is mounted 42 inches from the rear wall. Provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29(b).

 

                        6)        The rear grab bar at the toilet is inaccessible because it is 30 inches long and the far end is mounted 34 inches from the side wall. Provide a rear grab bar that is at least 36 inches in overall length with the far end mounted at least 48 inches from the side wall and the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29.

 

                        7)        The rear grab bar at the toilet is inaccessible because the soap dispenser interferes with the clear space above the bar and prevents access to the bar. Provide a rear grab bar that has at least 1½ inches between the grab bar and any object beside or below it and at least 18 inches between the grab bar and any object above it. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, 4.26.2, Fig. 39.

 

            P.        Women’s Toilet Room: Single-User – Kaufman Deliberation Room – 6th floor

 

                        1)        The door to the unisex toilet room, which is accessed from the latch side of the door, is inaccessible because it has only 14½ inches of maneuvering clearance. On the pull side of the door, provide a path of travel at least 48 inches wide for a side approach and at least 24 inches of clear maneuvering space adjacent to the latch side of the door. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(c).

 

                        2)        The toilet is inaccessible because its centerline measures 19½ inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.2, Fig. 28.

 

                        3)        The side grab bar at the toilet is inaccessible because it is 36 inches long and the far end is mounted 42 inches from the rear wall. Provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29(b).

 

                        4)        The rear grab bar at the toilet is inaccessible because it is 30 inches long and the far end is mounted 34 inches from the side wall. Provide a rear grab bar that is at least 36 inches in overall length with the far end mounted at least 48 inches from the side wall and the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29.

 

                        5)        The rear grab bar at the toilet is inaccessible because the soap dispenser interferes with it. Provide a rear grab bar that has at least 1½ inches between the grab bar and any object beside or below it and at least 18 inches between the grab bar and any object above it. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, 4.26.2, Fig. 39.

 

            Q.        Unisex Toilet Rooms: Single-User – 4th, 5th, 6th and 7th floor Holding Cells

 

                        1)        The side grab bar at the toilet is inaccessible because it is 39 inches long and the far end is mounted 43 inches from the rear wall. Provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29(b).

 

                        2)        The rear grab bar at the toilet is inaccessible because it is 20 inches long and the far end is mounted 23 inches from the side wall. Provide a rear grab bar that is at least 36 inches in overall length with the far end mounted at least 48 inches from the side wall and the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29.

 

                        3)        The lavatory is inaccessible because the drain cover interferes with the knee space under the lavatory. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, Fig. 31.

 

                        4)        The toilet is inaccessible because the flush control is mounted on the closed side of the toilet. Provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.27.4.

 

            R.        Men’s Toilet Room: Single-User – Stucky Courtroom – 6th floor

 

                        1)        The courtroom door is inaccessible because knob hardware is used. Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.9.

 

                        2)        No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.

 

                        3)        The toilet is inaccessible because the top of the seat is less than 17 inches above the finished floor. Provide a toilet with a seat that measures 17 to 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.3, Fig. 29(b).

 

                        4)        The side grab bar at the toilet is inaccessible because it is 36 inches long and the far end is mounted 42 inches from the rear wall. Provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29(b).

 

                        5)        The rear grab bar at the toilet is inaccessible because the soap dispenser interferes with the clear space above the bar and prevents access to the bar Provide a rear grab bar that has at least 1½ inches between the grab bar and any object beside or below it and at least 18 inches between the grab bar and any object above it. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, 4.26.2, Fig. 39.

 

                        6)        The rear grab bar at the toilet is inaccessible because it is only 30 inches long and is mounted with the far side only 34 inches from the side wall. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29.

 

            S.        Unisex Toilet Room: Single-User – Stucky Courtroom – 6th floor

 

                        1)        There is no signage directing people with disabilities to the accessible toilet rooms. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible toilet rooms indicating the location of the nearest accessible toilet room, and provide accessible signage with the International Symbol of Accessibility at all accessible toilet rooms. Standards §§ 4.1.2(7)(d), 4.1.6(3)(e)(iii), 4.30.1, 4.30.2, 4.30.3, 4.30.5, 4.30.7.

 

                        2)        The pull side of the door to the unisex toilet room, which is accessed from the latch side of the door, is inaccessible because it has only 15 inches of maneuvering clearance from the door to the lavatory. On the pull side of the door, provide a path of travel at least 48 inches wide for a side approach and at least 24 inches of clear maneuvering space adjacent to the latch side of the door. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(c).

 

                        3)        The push side of the door to the unisex toilet room, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 6½ inches of maneuvering clearance. On the push side of the door, provide maneuvering clearance at least 48 inches deep and provide a minimum of 12 inches of maneuvering clearance on the latch side of the door, or remove the closer or the latch. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).

 

                        4)        The side grab bar at the toilet is inaccessible because it is 36 inches long and the far end is mounted 42 inches from the rear wall. Provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29(b).

 

                        5)        The side grab bar at the toilet is inaccessible because it is obstructed by the toilet seat cover dispenser. Provide a side grab bar that has at least 1½ inches between the grab bar and any other object, such as the toilet paper dispenser. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, 4.26.2, Fig. 39.

 

                        6)        The rear grab bar at the toilet is inaccessible because it is only 30 inches long and is mounted with the farther end only 34 inches from the side wall. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29.

 

                        7)        The rear grab bar at the toilet is inaccessible because the soap dispenser interferes with the clear space above the bar and prevents access to the bar. Provide a rear grab bar that has at least 1½ inches between the grab bar and any object beside or below it and at least 18 inches between the grab bar and any object above it. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, 4.26.2, Fig. 39.

 

            T.        Men’s Toilet Room: Single-User – 5th floor

 

                        1)        The men’s toilet room door is inaccessible because the pressure required to open the door is 16 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

                        2)        The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 15½ inches of maneuvering clearance. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).

 

                        3)        The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 4½ inches of maneuvering clearance. On the push side of the door, provide maneuvering clearance at least 48 inches deep and provide a minimum of 12 inches of maneuvering clearance on the latch side of the door, or remove the closer or the latch. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).

 

                        4)        The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.4.

 

                        5)        The toilet paper dispenser is inaccessible because it is mounted 45 inches from the rear wall. Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.6, Fig. 29(b).

 

                        6)        The side grab bar at the toilet is inaccessible because the far end is mounted 50 inches from the rear wall. Provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29(b).

 

            U.        Women’s Toilet Room: Single-User – 5th floor

 

                        1)        The women’s toilet room door is inaccessible because the pressure required to open the door is 16 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

                        2)        The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 8 inches of maneuvering clearance. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).

 

                        3)        The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 8 inches of maneuvering clearance. On the push side of the door, provide maneuvering clearance at least 48 inches deep and provide a minimum of 12 inches of maneuvering clearance on the latch side of the door, or remove the closer or the latch. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).

 

                        4)        The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.4.

 

                        5)        The toilet paper dispenser is inaccessible because it is 18½ inches high and mounted 43½ inches from the rear wall. Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.6, Fig. 29(b).

 

                        6)        The side grab bar at the toilet is inaccessible because the far end is mounted 50 inches from the rear wall. Provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29(b).

 

                        7)        The rear grab bar at the toilet is inaccessible because it is obstructed by the toilet seat cover dispenser. Provide a rear grab bar that has at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, 4.26.2, Fig. 39.

 

            V.        Men’s Toilet Room: Single-User – Bloom Courtroom – 5th floor