| Barrier Number |
Floor |
Location Number |
Description |
Condition |
Barrier notes |
Standards |
| 2 |
Ext. |
E-102 |
Curb Ramp |
10 - 10.4% slope |
Slope of existing Curb Ramp in the direction of
travel exceeds 1:12 (8.3%). |
4.7.2; Fig. 11 |
| 3 |
Ext. |
E-102 |
Curb Ramp |
2.3 - 3% cross slope |
Cross slope of existing Curb Ramp (perpendicular to
the direction of travel) exceeds 1:50 (2%). |
4.7.2 |
| 4 |
Ext. |
E-102 |
Curb Ramp |
19.3% flared side |
Existing Curb Ramp flared sides exceed 10%. |
4.7.5; Fig. 12 |
| 5 |
Ext. |
E-103 |
Curb Ramp |
2.5% cross slope |
Cross slope of existing Curb Ramp (perpendicular to
the direction of travel) exceeds 1:50 (2%). |
4.7.2 |
| 6 |
Ext. |
E-103 |
Curb Ramp |
15.8% flared side |
Existing Curb Ramp flared sides exceed 10%. |
4.7.5; Fig. 12 |
| 12 |
Ext. |
E-106 |
Curb Ramp |
17.1% flared side |
Existing Curb Ramp flared sides exceed 10%. |
4.7.5; Fig. 12 |
| 13 |
Ext. |
E-107 |
Curb Ramp |
19% flared side |
Existing Curb Ramp flared sides exceed 10%. |
4.7.5; Fig. 12 |
| 15 |
Ext. |
E-109 |
Curb Ramp |
9% slope |
Slope of existing Curb Ramp in the direction of
travel exceeds 1:12 (8.3%). |
4.7.2; Fig. 11 |
| 16 |
Ext. |
E-109 |
Curb Ramp |
Less than 24" straight curb |
Existing diagonal, or corner-type, Curb Ramp has
flared sides, but does not have at least 24" length of straight curb
also within marked crossing. Defendants will address by contacting New York
City agencies/entities with authority to re-paint crosswalk. |
4.7.10; Fig. 15 |
| 19 |
Ext. |
E-111 |
Curb Ramp |
9.1 - 9.9% slope |
Slope of existing Curb Ramp in the direction of
travel exceeds 1:12 (8.3%). |
4.7.2; Fig. 11 |
| 22 |
Ext. |
E-114 |
Curb Ramp |
Less than 24" straight curb |
Existing diagonal, or corner-type, Curb Ramp has
flared sides, but does not have at least 24" length of straight curb
also within marked crossing. Defendants will address by contacting New York
City agencies/entities with authority to re-paint crosswalk. |
4.7.10; Fig. 15 |
| 267 |
01 |
C-121 |
Lobby |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 283 |
02 |
A-104 |
Concourse Ramp |
No handrail |
Ramp > 6" high, or > 72" long with
no handrail. |
4.8.5 |
| 372 |
02 |
A-125 |
Ticket Counter |
Inconspicuous signs regarding assistive listening
device |
No signage is provided at the ticket office or other
apparent location notifying patrons of the availability of an Assistive
Listening System. |
4.1.3(19)(b) |
| 373 |
02 |
A-125 |
Ticket Counter |
42" AFF |
Sales, Service or Information Counter(s) or Teller
Window(s) higher than 36" AFF or at Cash Register(s) for sales or
distribution of goods or services to the public. Twenty-three counters, none
accessible. |
7.2 |
| 377 |
02 |
A-129 |
Madison Square Garden Bridge Lobby |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 378 |
02 |
A-130 |
Madison Square Garden Bridge Lobby |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 382 |
02 |
A-132 |
Madison Square Garden Lobby |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 383 |
02 |
A-133 |
Visual Alarm in Concourse by Escalator |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 384 |
02 |
A-134 |
Visual Alarm in Concourse by Escalator Column 22 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 726 |
02 |
B-125 |
Visual Alarm in Concourse by Escalator Column 30 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 727 |
02 |
B-126 |
Visual Alarm in Concourse by Escalator Column 26 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 824 |
02 |
C-114 |
Visual Alarm in Concourse by Column 43 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 825 |
02 |
C-115 |
Visual Alarm in Concourse by Column 45 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 826 |
02 |
C-116 |
Visual Alarm in Concourse by Column 1 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 833 |
02 |
D-103 |
Concourse Ramp |
No handrail |
Ramp > 6" high, or > 72" long with
no handrail. |
4.8.5 |
| 853 |
02 |
D-114 |
Madison Square Garden Bridge Lobby |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 854 |
02 |
D-115 |
Visual Alarm in Concourse by Escalator Column 9 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 855 |
02 |
D-116 |
Visual Alarm in Concourse by Escalator Column 5 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 1814 |
06 |
000 |
Public Pay Telephone |
No forward approach phone |
Two or more banks of public pay telephones on this
floor. None meet the requirements for a forward reach telephone, where a
minimum of 1 per floor is required. |
4.1.3(17)(a) |
| 1815 |
06 |
A-101 |
Lighted Signs |
5.5" projection, 34.5" AFF |
Protruding object with bottom between 27" and
80" AFF projects more than 4" from wall or 12" from post. |
4.4.1; Fig. 8a-d |
| 1816 |
06 |
A-102 |
Public Pay Telephone |
No outlet |
Bank of 3 or more phones: None have shelf or outlet
for portable TTY. |
4.1.3(17)(d) |
| 1817 |
06 |
A-102 |
Public Pay Telephone |
65" AFF |
Operable parts of phone outside reach range; five
public pay telephones, none accessible |
4.1.3(17), 4.31.3; Fig. 5, 6, 44a-b |
| 1818 |
06 |
A-102 |
Public Pay Telephone |
No volume control |
Accessible telephone does not have volume control. |
4.1.3(17)(b) |
| 1819 |
06 |
A-102 |
Public Pay Telephone |
Grasping and twisting |
Push button controls are required: Operable part of
telephone requires grasping or twisting to operate |
4.31.6 |
| 1820 |
06 |
A-103 |
Gift and Souvenir Counter |
42" AFF |
Sales, Service or Information Counter(s) or Teller
Window(s) higher than 36" AFF or at Cash Register(s) for sales or
distribution of goods or services to the public. |
7.2 |
| 1821 |
06 |
A-104 |
ATM |
All Instructions on ATM screen |
Instructions and/or Information for use not
accessible to and independently usable by persons with visual impairments. |
4.34.5 |
| 1822 |
06 |
A-105 |
Concession Counter |
41.75" AFF |
Sales, Service or Information Counter(s) or Teller
Window(s) higher than 36" AFF: At Cash Register(s) for sales or
distribution of goods or services to the public. |
7.2 |
| 1824 |
06 |
A-107 |
Women's Toilet Room |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 1825 |
06 |
A-107 |
Women's Toilet Room |
No raised lettering and Braille |
Existing room and/or gender identification signage
is noncompliant. |
4.1.3(16)(a), 4.30.4 |
| 1826 |
06 |
A-107 |
Women's Toilet Room |
Sign above arch |
Existing room and/or identification sign is
incorrectly located. |
4.30.6 |
| 1827 |
06 |
A-107 |
Women's Toilet Room |
12 stalls, 0 ambulatory |
If greater than or equal to 6, and if standard
accessible stall provided, 36" wide ambulatory accessible stall also
required. |
4.1.3(11), 4.22.4; Fig. 30d |
| 1830 |
06 |
A-107 |
Women's Toilet Room |
66.5" AFF |
Coat hook > 48" above finish floor front
reach, or > 54"; side reach. |
4.22.7, 4.27.3; Fig. 5, 6 |
| 1831 |
06 |
A-107 |
Women's Toilet Room |
9.5" corner |
Rear Wall grab bar > 6" from side wall or
(partition) nearest water closet. |
4.1.3(11), 4.22.4, 4.16.4, 4.17.6; Fig. 29, 30 |
| 1832 |
06 |
A-107 |
Women's Toilet Room |
27" centerline |
Centerline of water closet is < or > 18"
from sidewall or partition. |
4.1.3(11), 4.22.4, 4.16.2, 4.17.3; Fig. 28, 30 |
| 1834 |
06 |
A-107 |
Women's Toilet Room |
27# |
Manual flush control at water closet requires > 5
lbs. of force to activate. |
4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4 |
| 1835 |
06 |
A-107 |
Women's Toilet Room |
Toilet tissue on far wall |
Toilet paper dispenser located other than side wall
nearest water closet. |
4.1.3(11), 4.22.4, 4.16.6, 4.17.2; Fig. 29b, 30(d) |
| 1836 |
06 |
A-107 |
Women's Toilet Room |
Large roll toilet paper |
Large roll toilet paper dispenser requires pinching
and does not allow continuous delivery. |
4.1.3(11), 4.22.4, 4.16.6, 4.17.2; Fig. 29b, 30(d) |
| 1837 |
06 |
A-107 |
Women's Toilet Room |
26.5" wide |
Clearance < 30" x 48" at lavatory. |
4.1.3(11), 4.22.6, 4.19.3; Fig. 32 |
| 1838 |
06 |
A-107 |
Women's Toilet Room |
No insulation |
Hot water pipes not insulated or covered. |
4.1.3(11), 4.22.6, 4.19.4 |
| 1839 |
06 |
A-107 |
Women's Toilet Room |
67" AFF |
Towel dispenser or blower outside reach range. |
4.1.3(11), 4.22.7, 4.27.3; Fig. 4, 5, 6 |
| 1840 |
06 |
A-107 |
Women's Toilet Room |
5.5" projection, 31" AFF |
Protruding object with bottom between 27" and
80" above finish floor projects > 4" from wall into circulation
path. |
4.4.1, 4.4.2; Fig. 8 |
| 1841 |
06 |
A-107 |
Women's Toilet Room |
16# |
Control or operating mechanism takes > 5 lbs.
force to operate or requires tight gripping, grasping or twisting of wrist.
Soap dispenser. |
4.1.3(11), 4.22.7, 4.27.4 |
| 1842 |
06 |
A-108 |
Public Pay Telephone |
No volume control |
Accessible telephone does not have volume control. |
4.1.3(17)(b) |
| 1843 |
06 |
A-108 |
Public Pay Telephone |
Grasping and twisting |
Push button controls are required: Operable part of
telephone requires grasping or twisting to operate |
4.31.6 |
| 1845 |
06 |
A-110 |
Condiment Counter |
14" projection, 35" AFF |
Protruding object with bottom between 27" and
80" AFF projects more than 4" from wall or 12" from post. |
4.4.1; Fig. 8a-d |
| 1846 |
06 |
A-110 |
Condiment Counter |
42.25" AFF |
Table or counter top < 28" AFF, or >
34" AFF. |
4.1.3(18), 4.32.4, 5.2 |
| 1848 |
06 |
A-111 |
Lobby Doors |
2 seconds |
Existing Closer causes Door to travel from 70
degrees open to 3" from latch in less than 3 sec. |
4.13.10 |
| 1849 |
06 |
A-112 |
Drinking Fountain |
41" AFF |
Spout outlet higher than 36" AFF. |
4.15.2 |
| 1850 |
06 |
A-112 |
Drinking Fountain |
11# |
Controls require more than 5# force to operate. |
4.15.4, 4.27.4 |
| 1851 |
06 |
A-113 |
Bar/Pub: Counter Around Wall |
5.75" projection, 41.75" AFF |
Protruding object with bottom between 27" and
80" AFF projects more than 4" from wall or 12" from post. |
4.4.1; Fig. 8a-d |
| 1852 |
06 |
A-113 |
Bar/Pub: Counter Around Column |
7" projection, 40.75" AFF |
Protruding object with bottom between 27" and
80" AFF projects more than 4" from wall or 12" from post. |
4.4.1; Fig. 8a-d |
| 1853 |
06 |
A-113 |
Bar/Pub: Display Television |
8.25" projection, 57.25" AFF |
Protruding object with bottom between 27" and
80" AFF projects more than 4" from wall or 12" from post. |
4.4.1; Fig. 8a-d |
| 1854 |
06 |
A-113 (near D-106) |
First Aid Room: Door from Concourse |
30" clear |
Clearance width < 32" at single doorway.
(Deduct 5/8" from width criteria for Alt. Tech. Infeas.) |
4.13.5; Fig. 24 |
| 1856 |
06 |
A-113 (near D-106) |
First Aid Room: Door from Concourse |
Knob |
Existing door hardware requires tight grasping,
pinching, or twisting of the wrist to operate. |
4.13.9 |
| 1858 |
06 |
A-113 (near D-106) |
First Aid Room: Door from Concourse |
12# |
Force to operate interior non-fire-rated door
exceeds 5#. |
4.13.11(2)(b) |
| 1859 |
06 |
A-113 (near D-106) |
First Aid Room: Door from Concourse |
Sign on door, no raised lettering and Braille |
Existing room identification signage is
noncompliant. |
4.1.3(16)(a) |
| 1860 |
06 |
A-113 (near D-106) |
First Aid Room |
No visual alarm |
An audible alarm system is provided within this
building. A visual signal is not provided in this common use area. |
4.1.3(14), 4.28.1 |
| 1861 |
06 |
A-113 |
Bar/Pub |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 1862.1 |
06 |
A-113 (near D-106) |
First Aid Room: Toilet Room |
Inaccessible; no directional signage |
No directional signage to nearest accessible toilet
room at inaccessible toilet room. |
4.1.6(3)(e)(iii) |
| 1873 |
06 |
A-113 |
Bar/Pub: Drink Counter |
42.5" AFF |
Food or Drink served to customers at Counter or Bar
on stools or standing, but no section meets accessibility requirements. |
5.2 |
| 1874 |
06 |
A-113 |
Bar/Pub: Concession Counter |
43.5" AFF |
Sales, Service or Information Counter(s) or Teller
Window(s) higher than 36" AFF or at Cash Register(s) for sales or
distribution of goods or services to the public. |
7.2 |
| 1875 |
06 |
A-114 |
Team Store |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 1876 |
06 |
A-114 |
Team Store: Sales Counter |
42" AFF |
Sales, Service or Information Counter(s) or Teller
Window(s) higher than 36" AFF or at Cash Register(s) for sales or
distribution of goods or services to the public. |
7.2 |
| 1877 |
06 |
A-115 |
Visual Alarm in Concourse by Column 15 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 1878 |
06 |
A-116 |
Visual Alarm in Concourse by Column 18 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 1879 |
06 |
A-117 |
Visual Alarm in Concourse by Column 20 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 1880 |
06 |
A-118 |
Fire Pull at Column 18 |
63" AFF |
Control outside reach range. |
4.1.3(13), 4.27.3; Fig. 5, 6 |
| 1881 |
06 |
B-101 |
Public Pay Telephone |
No shelf or outlet |
Bank of 3 or more phones: None have shelf or outlet
for portable TTY. |
4.1.3(17)(d) |
| 1882 |
06 |
B-101 |
Public Pay Telephone |
55.5" AFF |
Operable parts of phone outside reach range.n Four
public pay telephones, none accessible. |
4.1.3(17), 4.31.3; Fig. 5, 6, 44a-b |
| 1883 |
06 |
B-101 |
Public Pay Telephone |
Grasping and twisting |
Push button controls are required: Operable part of
telephone requires grasping or twisting to operate |
4.31.6 |
| 1884 |
06 |
B-101 |
Public Pay Telephone |
No TTY |
4 or more Public Pay Phones, interior and exterior,
at this site, and no interior TTY. |
4.1.3(17)(c)(i) and (ii) |
| 1885 |
06 |
B-102 |
Lighted Sign |
5.5" projection, 38.5" AFF |
Protruding object with bottom between 27" and
80" AFF projects more than 4" from wall or 12" from post. |
4.4.1; Fig. 8a-d |
| 1886 |
06 |
B-103 |
Women's Toilet Room |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 1887 |
06 |
B-103 |
Women's Toilet Room |
No raised lettering and Braille |
Existing room and/or gender identification signage
is noncompliant. |
4.1.3(16)(a), 4.30.4 |
| 1888 |
06 |
B-103 |
Women's Toilet Room |
Sign above arch |
Existing room and/or identification sign is
incorrectly located. |
4.30.6 |
| 1889.1 |
06 |
B-103 |
Women's Toilet Room |
Inaccessible; no directional signage |
No directional signage to nearest accessible toilet
room at inaccessible toilet room. |
4.1.6(3)(e)(iii) |
| 1900 |
06 |
B-104 |
Men's Toilet Room |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 1901 |
06 |
B-104 |
Men's Toilet Room |
No raised lettering and Braille |
Existing room and/or gender identification signage
is noncompliant. |
4.1.3(16)(a), 4.30.4 |
| 1902 |
06 |
B-104 |
Men's Toilet Room |
Sign above arch |
Existing room and/or identification sign is
incorrectly located. |
4.30.6 |
| 1903.1 |
06 |
B-104 |
Men's Toilet Room |
Inaccessible; no directional signage |
No directional signage to nearest accessible toilet
room at inaccessible toilet room. |
4.1.6(3)(e)(iii) |
| 1917 |
06 |
B-105 |
Eating Counter |
16" projection, 38.5" AFF |
Protruding object with bottom between 27" and
80" AFF projects more than 4" from wall or 12" from post. |
4.4.1; Fig. 8a-d |
| 1918 |
06 |
B-105 |
Eating Counter |
42.5" AFF |
Table or counter top < 28" AFF, or >
34" AFF. |
4.1.3(18), 4.32.4, 5.2 |
| 1919 |
06 |
B-106 |
Moveable Eating Tables |
39" AFF |
Table or counter top < 28" AFF, or >
34" AFF. |
4.1.3(18), 4.32.4, 5.2 |
| 1924 |
06 |
B-107 |
Men's Toilet Room |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 1925 |
06 |
B-107 |
Men's Toilet Room |
No raised lettering and Braille |
Existing room and/or gender identification signage
is noncompliant. |
4.1.3(16)(a), 4.30.4 |
| 1926 |
06 |
B-107 |
Men's Toilet Room |
Sign above arch |
Existing room and/or identification sign is
incorrectly located. |
4.30.6 |
| 1927 |
06 |
B-107 |
Men's Toilet Room |
6 stalls, 0 ambulatory |
If greater than or equal to 6, and if standard
accessible stall provided, 36" wide ambulatory accessible stall also
required. |
4.1.3(11), 4.22.4; Fig. 30d |
| 1928 |
06 |
B-107 |
Men's Toilet Room |
38.5" wide |
Accessible stall width < 60". |
4.1.3(11), 4.22.4, 4.17.3; Fig. 30d |
| 1930 |
06 |
B-107 |
Men's Toilet Room |
66.5" AFF |
Coat hook > 48" above finish floor front
reach, or > 54"; side reach. |
4.22.7, 4.27.3; Fig. 5, 6 |
| 1931 |
06 |
B-107 |
Men's Toilet Room |
No rear grab bar |
No rear grab bar (except at 36" alternate
accessible stall). |
4.1.3(11), 4.22.4, 4.16.4, 4.17.6; Fig. 29, 30 |
| 1932 |
06 |
B-107 |
Men's Toilet Room |
13# |
Manual flush control at water closet requires > 5
lbs. of force to activate. |
4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4 |
| 1933 |
06 |
B-107 |
Men's Toilet Room |
Large roll toilet paper |
Large roll toilet paper dispenser requires pinching
and does not allow continuous delivery. |
4.1.3(11), 4.22.4, 4.16.6, 4.17.2; Fig. 29b, 30(d) |
| 1934 |
06 |
B-107 |
Men's Toilet Room |
46.5" AFF |
Manual flush control at urinal > 44" above
finished floor. |
4.1.3(11), 4.22.5, 4.18.4 |
| 1935 |
06 |
B-107 |
Men's Toilet Room |
12# |
Manual flush control at urinal requires > five
pounds force to activate. |
4.1.3(11), 4.22.5, 4.18.4, 4.27.4 |
| 1937 |
06 |
B-107 |
Men's Toilet Room |
27" wide |
Clearance < 30" x 48" at lavatory. |
4.1.3(11), 4.22.6, 4.19.3; Fig. 32 |
| 1938 |
06 |
B-107 |
Men's Toilet Room |
No insulation |
Hot water pipes not insulated or covered. |
4.1.3(11), 4.22.6, 4.19.4 |
| 1939 |
06 |
B-107 |
Men's Toilet Room |
66" AFF |
Towel dispenser or blower outside reach range. |
4.1.3(11), 4.22.7, 4.27.3; Fig. 4, 5, 6 |
| 1940 |
06 |
B-107 |
Men's Toilet Room |
5.25" projection, 31.5" AFF |
Protruding object with bottom between 27" and
80" above finish floor projects > 4" from wall into circulation
path. |
4.4.1, 4.4.2; Fig. 8 |
| 1941 |
06 |
B-107 |
Men's Toilet Room |
16# |
Control or operating mechanism takes > 5 lbs.
force to operate or requires tight gripping, grasping or twisting of wrist.
Soap dispenser. |
4.1.3(11), 4.22.7, 4.27.4 |
| 1942 |
06 |
B-108 |
Lighted Sign |
5.5" projection, 30.5" AFF |
Protruding object with bottom between 27" and
80" AFF projects more than 4" from wall or 12" from post. |
4.4.1; Fig. 8a-d |
| 1943 |
06 |
B-109 |
Concession Counter |
41.25" AFF |
Sales, Service or Information Counter(s) or Teller
Window(s) higher than 36" AFF or at Cash Register(s) for sales or
distribution of goods or services to the public. |
7.2 |
| 1944 |
06 |
B-110 |
Guest Services Counter |
42" AFF |
Sales, Service or Information Counter(s) or Teller
Window(s) higher than 36" AFF or at Cash Register(s) for sales or
distribution of goods or services to the public. |
7.2 |
| 1963 |
06 |
B-117 |
Public Pay Telephone |
Grasping and twisting |
Push button controls are required: Operable part of
telephone requires grasping or twisting to operate |
4.31.6 |
| 1965 |
06 |
B-118 |
Condiment Counter |
14" projection, 34.5" AFF |
Protruding object with bottom between 27" and
80" AFF projects more than 4" from wall or 12" from post. |
4.4.1; Fig. 8a-d |
| 1966 |
06 |
B-118 |
Public Pay Telephone |
No volume control |
Accessible telephone does not have volume control. |
4.1.3(17)(b) |
| 1967 |
06 |
B-118 |
Public Pay Telephone |
Grasping and twisting |
Push button controls are required: Operable part of
telephone requires grasping or twisting to operate |
4.31.6 |
| 1968 |
06 |
B-118 |
Condiment Counter |
42.5" AFF |
Table or counter top < 28" AFF, or >
34" AFF. |
4.1.3(18), 4.32.4, 5.2 |
| 1970 |
06 |
B-119 |
Elevator Lobby |
Jamb identification, 1 side only |
Floor Designations at Elevator Hoistway are not
located on both jambs of Hoistway openings. |
4.10.5; Fig. 20 |
| 1972 |
06 |
B-120 |
Lobby Doors |
2 seconds |
Existing Closer causes Door to travel from 70
degrees open to 3" from latch in less than 3 sec. |
4.13.10 |
| 1973 |
06 |
B-121 |
Condiment Counter |
14" projection, 34.25" AFF |
Protruding object with bottom between 27" and
80" AFF projects more than 4" from wall or 12" from post. |
4.4.1; Fig. 8a-d |
| 1974 |
06 |
B-121 |
Condiment Counter |
41.75" AFF |
Table or counter top < 28" AFF, or >
34" AFF. |
4.1.3(18), 4.32.4, 5.2 |
| 2037 |
06 |
B-130 |
Two Elevators |
No signal |
Existing Car Position Indicator does not give an
Audible Signal. |
4.10.4 |
| 2039 |
06 |
B-135 |
Visual Alarm in Corridor by Column 31 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2040 |
06 |
B-136 |
Visual Alarm in Corridor by Column 28 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2041 |
06 |
B-137 |
Visual Alarm in Corridor by Column 24 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2046 |
06 |
B-139 |
Fire Pull at Column 30 |
62.5" AFF |
Control outside reach range. |
4.1.3(13), 4.27.3; Fig. 5, 6 |
| 2049 |
06 |
B-140 |
Fire Pull at Column 25 |
63" AFF |
Control outside reach range. |
4.1.3(13), 4.27.3; Fig. 5, 6 |
| 2052 |
06 |
C-101 |
Women's Toilet Room |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2053 |
06 |
C-101 |
Women's Toilet Room |
No raised lettering and Braille |
Existing room and/or gender identification signage
is noncompliant. |
4.1.3(16)(a), 4.30.4 |
| 2054 |
06 |
C-101 |
Women's Toilet Room |
Sign above arch |
Existing room and/or identification sign is
incorrectly located. |
4.30.6 |
| 2055.1 |
06 |
C-101 |
Women's Toilet Room |
Inaccessible; no directional signage |
No directional signage to nearest accessible toilet
room at inaccessible toilet room. |
4.1.6(3)(e)(iii) |
| 2067 |
06 |
C-102 |
Eating Counter |
16" projection, 37.75" AFF |
Protruding object with bottom between 27" and
80" AFF projects more than 4" from wall or 12" from post. |
4.4.1; Fig. 8a-d |
| 2068 |
06 |
C-102 |
Eating Counter |
41.75" AFF |
Table or counter top < 28" AFF, or >
34" AFF. |
4.1.3(18), 4.32.4, 5.2 |
| 2069 |
06 |
C-103 |
Moveable Eating Tables |
39" AFF |
Table or counter top < 28" AFF, or >
34" AFF. |
4.1.3(18), 4.32.4, 5.2 |
| 2075 |
06 |
C-105 |
Public Pay Telephone |
No outlet |
Bank of 3 or more phones: None have shelf or outlet
for portable TTY. |
4.1.3(17)(d) |
| 2076 |
06 |
C-105 |
Public Pay Telephone |
65" AFF |
Operable parts of phone outside reach range. Five
public pay telephones, none accessible. |
4.1.3(17), 4.31.3; Fig. 5, 6, 44a-b |
| 2077 |
06 |
C-105 |
Public Pay Telephone |
No volume control |
Accessible telephone does not have volume control. |
4.1.3(17)(b) |
| 2078 |
06 |
C-105 |
Public Pay Telephone |
Grasping and twisting |
Push button controls are required: Operable part of
telephone requires grasping or twisting to operate |
4.31.6 |
| 2079 |
06 |
C-106 |
Gift and Souvenir Counter |
42" AFF |
Sales, Service or Information Counter(s) or Teller
Window(s) higher than 36" AFF or at Cash Register(s) for sales or
distribution of goods or services to the public. |
7.2 |
| 2150 |
06 |
C-110 |
Lighted Sign |
5.5" projection, 38.5" AFF |
Protruding object with bottom between 27" and
80" AFF projects more than 4" from wall or 12" from post. |
4.4.1; Fig. 8a-d |
| 2151 |
06 |
C-111 |
Concession Counter |
41.5" AFF |
Sales, Service or Information Counter(s) or Teller
Window(s) higher than 36" AFF or at Cash Register(s) for sales or
distribution of goods or services to the public. |
7.2 |
| 2152 |
06 |
C-112 |
Lighted Sign |
5.5" projection, 30" AFF |
Protruding object with bottom between 27" and
80" AFF projects more than 4" from wall or 12" from post. |
4.4.1; Fig. 8a-d |
| 2153 |
06 |
C-113 |
Women's Toilet Room |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2154 |
06 |
C-113 |
Women's Toilet Room |
No raised lettering and Braille |
Existing room and/or gender identification signage
is noncompliant. |
4.1.3(16)(a), 4.30.4 |
| 2155 |
06 |
C-113 |
Women's Toilet Room |
Sign above arch |
Existing room and/or identification sign is
incorrectly located. |
4.30.6 |
| 2156 |
06 |
C-113 |
Women's Toilet Room |
12 stalls, 0 ambulatory |
If greater than or equal to 6, and if standard
accessible stall provided, 36" wide ambulatory accessible stall also
required. |
4.1.3(11), 4.22.4; Fig. 30d |
| 2158 |
06 |
C-113 |
Women's Toilet Room |
66.5" AFF |
Coat hook > 48" above finish floor front
reach, or > 54"; side reach. |
4.22.7, 4.27.3; Fig. 5, 6 |
| 2160 |
06 |
C-113 |
Women's Toilet Room |
19.5" centerline |
Centerline of water closet is < or > 18"
from sidewall or partition. |
4.1.3(11), 4.22.4, 4.16.2, 4.17.3; Fig. 28, 30 |
| 2161 |
06 |
C-113 |
Women's Toilet Room |
Narrow side |
Manual flush control is not located on open side of
water closet. |
4.1.3(11), 4.22.4, 4.16.5, 4.17.2 |
| 2162 |
06 |
C-113 |
Women's Toilet Room |
13# |
Manual flush control at water closet requires > 5
lbs. of force to activate. |
4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4 |
| 2163 |
06 |
C-113 |
Women's Toilet Room |
Large roll toilet paper |
Large roll toilet paper dispenser requires pinching
and does not allow continuous delivery. |
4.1.3(11), 4.22.4, 4.16.6, 4.17.2; Fig. 29b, 30(d) |
| 2164 |
06 |
C-113 |
Women's Toilet Room |
No insulation |
Hot water pipes not insulated or covered. |
4.1.3(11), 4.22.6, 4.19.4 |
| 2165 |
06 |
C-113 |
Women's Toilet Room |
67" AFF |
Towel dispenser or blower outside reach range. |
4.1.3(11), 4.22.7, 4.27.3; Fig. 4, 5, 6 |
| 2166 |
06 |
C-113 |
Women's Toilet Room |
5.25" AFF, 31" AFF |
Protruding object with bottom between 27" and
80" above finish floor projects > 4" from wall into circulation
path. |
4.4.1, 4.4.2; Fig. 8 |
| 2167 |
06 |
C-113 |
Women's Toilet Room |
12# |
Control or operating mechanism takes > 5 lbs.
force to operate or requires tight gripping, grasping or twisting of wrist.
Soap dispenser. |
4.1.3(11), 4.22.7, 4.27.4 |
| 2180 |
06 |
C-116 |
Condiment Counter |
14" projection, 34.75" AFF |
Protruding object with bottom between 27" and
80" AFF projects more than 4" from wall or 12" from post. |
4.4.1; Fig. 8a-d |
| 2181 |
06 |
C-116 |
Condiment Counter |
42.25" AFF |
Table or counter top < 28" AFF, or >
34" AFF. |
4.1.3(18), 4.32.4, 5.2 |
| 2184 |
06 |
C-118 |
Lobby Doors |
2 seconds |
Existing Closer causes Door to travel from 70
degrees open to 3" from latch in less than 3 sec. |
4.13.10 |
| 2186 |
06 |
C-120 |
Drinking Fountain |
41" AFF |
Spout outlet higher than 36" AFF. |
4.15.2 |
| 2187 |
06 |
C-120 |
Drinking Fountain |
3" waterflow |
Stream height less than 4". |
4.15.3 |
| 2188 |
06 |
C-120 |
Drinking Fountain |
10# |
Controls require more than 5# force to operate. |
4.15.4, 4.27.4 |
| 2189 |
06 |
C-121 |
Condiment Counters |
14" projection, 34.5" AFF |
Protruding object with bottom between 27" and
80" AFF projects more than 4" from wall or 12" from post. |
4.4.1; Fig. 8a-d |
| 2190 |
06 |
C-121 |
Public Pay Telephones |
No volume control |
Accessible telephone does not have volume control. |
4.1.3(17)(b) |
| 2191 |
06 |
C-121 |
Public Pay Telephones |
Grasping and twisting |
Push button controls are required: Operable part of
telephone requires grasping or twisting to operate |
4.31.6 |
| 2192 |
06 |
C-121 |
Condiment Counters |
42" AFF |
Table or counter top < 28" AFF, or >
34" AFF. |
4.1.3(18), 4.32.4, 5.2 |
| 2193 |
06 |
C-122 |
Public Pay Telephone |
No volume control |
Accessible telephone does not have volume control. |
4.1.3(17)(b) |
| 2194 |
06 |
C-122 |
Public Pay Telephone |
Grasping and twisting |
Push button controls are required: Operable part of
telephone requires grasping or twisting to operate |
4.31.6 |
| 2195 |
06 |
C-122 |
Public Pay Telephone |
27.75" AFF, 12" projection |
Telephone mounted with bottom between 27" and
80" AFF projects > 4" from the wall or > 12" from a
post. |
4.31.4, 4.4.1; Fig. 8a-e |
| 2243 |
06 |
C-124 |
Men's Toilet Room |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2244 |
06 |
C-124 |
Men's Toilet Room |
No raised lettering and Braille |
Existing room and/or gender identification signage
is noncompliant. |
4.1.3(16)(a), 4.30.4 |
| 2245 |
06 |
C-124 |
Men's Toilet Room |
Sign above arch |
Existing room and/or identification sign is
incorrectly located. |
4.30.6 |
| 2246.1 |
06 |
C-124 |
Men's Toilet Room |
Inaccessible; no directional signage |
No directional signage to nearest accessible toilet
room at inaccessible toilet room. |
4.1.6(3)(e)(iii) |
| 2259 |
06 |
C-125 |
Team Store: Wall Mounted Television by Cash Register |
21.25" projection, 63" AFF |
Protruding object with bottom between 27" and
80" AFF projects more than 4" from wall or 12" from post. |
4.4.1; Fig. 8a-d |
| 2260 |
06 |
C-125 |
Team Store: Ceiling Suspended Exit Sign |
77" AFF |
Head Room < 80" AFF clearance at Interior
Accessible Route. |
4.4.2; Fig. 8a-d |
| 2261 |
06 |
C-125 |
Team Store: Visual alarm |
78.5" AFF |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2262 |
06 |
C-125 |
Team Store: Sales Counter |
42" AFF |
Sales, Service or Information Counter(s) or Teller
Window(s) higher than 36" AFF or at Cash Register(s) for sales or
distribution of goods or services to the public. Five cash registers, none
accessible. |
7.2 |
| 2263 |
06 |
C-125 |
Team Store: Collectors Cash Register Counter |
40" AFF |
Sales, Service or Information Counter(s) or Teller
Window(s) higher than 36" AFF or at Cash Register(s) for sales or
distribution of goods or services to the public. |
7.2 |
| 2264 |
06 |
C-126 |
Visual Alarm in Concourse by Column 38 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2265 |
06 |
C-127 |
Visual Alarm in Concourse by Column 42 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2266 |
06 |
C-128 |
Visual Alarm in Concourse by Column 44 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2267 |
06 |
C-129 |
Visual Alarm in Concourse by Column 46 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2268 |
06 |
C-130 |
Visual Alarm in Concourse by Column 2 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2272 |
06 |
C-132 |
Fire Pull at Column 43 |
62.5" AFF |
Control outside reach range. |
4.1.3(13), 4.27.3; Fig. 5, 6 |
| 2273 |
06 |
C-133 |
Fire Pull at Column 1 |
64" AFF |
Control outside reach range. |
4.1.3(13), 4.27.3; Fig. 5, 6 |
| 2274 |
06 |
C-134 |
Bar: Eating Counter |
41.5" AFF, 8" projection |
Protruding object with bottom between 27" and
80" AFF projects more than 4" from wall or 12" from post. |
4.4.1; Fig. 8a-d |
| 2277 |
06 |
C-134 |
Bar: Tables |
42" AFF |
Less than 5% of Seating, Tables or Dining Counters
accessible overall, or in Smoking or Non-Smoking area. |
4.32, 5.1, |
| 2278 |
06 |
C-134 |
Bar: Bar Counter |
43" AFF |
Sales, Service or Information Counter(s) or Teller
Window(s) higher than 36" AFF or at Cash Register(s) for sales or
distribution of goods or services to the public. |
7.2 |
| 2279 |
06 |
D-101 |
Men's Toilet Room |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2280 |
06 |
D-101 |
Men's Toilet Room |
No raised lettering and Braille |
Existing room and/or gender identification signage
is noncompliant. |
4.1.3(16)(a), 4.30.4 |
| 2281 |
06 |
D-101 |
Men's Toilet Room |
Sign above arch |
Existing room and/or identification sign is
incorrectly located. |
4.30.6 |
| 2282 |
06 |
D-101 |
Men's Toilet Room |
6 stalls, 0 ambulatory |
If greater than or equal to 6, and if standard
accessible stall provided, 36" wide ambulatory accessible stall also
required. |
4.1.3(11), 4.22.4; Fig. 30d |
| 2283 |
06 |
D-101 |
Men's Toilet Room |
41" wide |
Accessible stall width < 60". |
4.1.3(11), 4.22.4, 4.17.3; Fig. 30a |
| 2285 |
06 |
D-101 |
Men's Toilet Room |
67" AFF |
Coat hook > 48" above finish floor front
reach, or > 54"; side reach. |
4.22.7, 4.27.3; Fig. 5, 6 |
| 2287 |
06 |
D-101 |
Men's Toilet Room |
No rear wall grab bar |
No rear grab bar (except at 36" alternate
accessible stall). |
4.1.3(11), 4.22.4, 4.16.4, 4.17.6; Fig. 29, 30 |
| 2288 |
06 |
D-101 |
Men's Toilet Room |
16.5" AFF |
Top of water closet seat <17" or >
19" above finish floor. |
4.1.3(11), 4.22.4, 4.16.3, 4.17.2; Fig. 29b, 30(d) |
| 2289 |
06 |
D-101 |
Men's Toilet Room |
13# |
Manual flush control at water closet requires > 5
lbs. of force to activate. |
4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4 |
| 2290 |
06 |
D-101 |
Men's Toilet Room |
Large roll toilet paper |
Large roll toilet paper dispenser requires pinching
and does not allow continuous delivery. |
4.1.3(11), 4.22.4, 4.16.6, 4.17.2; Fig. 29b, 30(d) |
| 2292 |
06 |
D-101 |
Men's Toilet Room |
15# |
Manual flush control at urinal requires > five
pounds force to activate. |
4.1.3(11), 4.22.5, 4.18.4, 4.27.4 |
| 2293 |
06 |
D-101 |
Men's Toilet Room |
No insulation |
Hot water pipes not insulated or covered. |
4.1.3(11), 4.22.6, 4.19.4 |
| 2294 |
06 |
D-101 |
Men's Toilet Room |
67" AFF |
Towel dispenser or blower outside reach range. |
4.1.3(11), 4.22.7, 4.27.3; Fig. 4, 5, 6 |
| 2295 |
06 |
D-101 |
Men's Toilet Room |
5.5" projection, 31" AFF |
Protruding object with bottom between 27" and
80" above finish floor projects > 4" from wall into circulation
path. |
4.4.1, 4.4.2; Fig. 8 |
| 2296 |
06 |
D-101 |
Men's Toilet Room |
16# |
Control or operating mechanism takes > 5 lbs.
force to operate or requires tight gripping, grasping or twisting of wrist.
Soap dispenser. |
4.1.3(11), 4.22.7, 4.27.4 |
| 2297 |
06 |
D-102 |
Lighted Sign |
5.5" projection, 30.25" AFF |
Protruding object with bottom between 27" and
80" AFF projects more than 4" from wall or 12" from post. |
4.4.1; Fig. 8a-d |
| 2298 |
06 |
D-103 |
Concession Counter |
42" AFF |
Sales, Service or Information Counter(s) or Teller
Window(s) higher than 36" AFF or at Cash Register(s) for sales or
distribution of goods or services to the public. |
7.2 |
| 2300 |
06 |
D-105 |
Public Pay Telephone |
65" AFF |
Operable parts of phone outside reach range. Three
public pay telephone, none accessible. |
4.1.3(17), 4.31.3; Fig. 5, 6, 44a-b |
| 2301 |
06 |
D-105 |
Public Pay Telephone |
No volume control |
Accessible telephone does not have volume control. |
4.1.3(17)(b) |
| 2302 |
06 |
D-105 |
Public Pay Telephone |
Grasping and twisting |
Push button controls are required: Operable part of
telephone requires grasping or twisting to operate |
4.31.6 |
| 2303 |
06 |
D-106 |
Public Pay Telephone |
No volume control |
Accessible telephone does not have volume control. |
4.1.3(17)(b) |
| 2304 |
06 |
D-106 |
Public Pay Telephone |
Grasping and twisting |
Push button controls are required: Operable part of
telephone requires grasping or twisting to operate |
4.31.6 |
| 2305 |
06 |
D-106 |
Public Pay Telephone |
12" projection, 28" AFF |
Telephone mounted with bottom between 27" and
80" AFF projects > 4" from the wall or > 12" from a
post. |
4.31.4, 4.4.1; Fig. 8a-e |
| 2306 |
06 |
D-107 |
Public Pay Telephone |
No volume control |
Accessible telephone does not have volume control. |
4.1.3(17)(b) |
| 2307 |
06 |
D-107 |
Public Pay Telephone |
Grasping and twisting |
Push button controls are required: Operable part of
telephone requires grasping or twisting to operate |
4.31.6 |
| 2308 |
06 |
D-107 |
Public Pay Telephone |
12" projection, 28" AFF |
Telephone mounted with bottom between 27" and
80" AFF projects > 4" from the wall or > 12" from a
post. |
4.31.4, 4.4.1; Fig. 8a-e |
| 2310 |
06 |
D-108 |
Lobby Doors |
2 seconds |
Existing Closer causes Door to travel from 70
degrees open to 3" from latch in less than 3 sec. |
4.13.10 |
| 2311 |
06 |
D-109 |
Condiment Counter |
14" projection, 35" AFF |
Protruding object with bottom between 27" and
80" AFF projects more than 4" from wall or 12" from post. |
4.4.1; Fig. 8a-d |
| 2312 |
06 |
D-110 |
Condiment Counter |
14" projection, 34.25" AFF |
Protruding object with bottom between 27" and
80" AFF projects more than 4" from wall or 12" from post. |
4.4.1; Fig. 8a-d |
| 2313 |
06 |
D-110 |
Condiment Counter |
42.25" AFF |
Table or counter top < 28" AFF, or >
34" AFF. |
4.1.3(18), 4.32.4, 5.2 |
| 2314 |
06 |
D-110 |
Condiment Counter |
41.75" AFF |
Table or counter top < 28" AFF, or >
34" AFF. |
4.1.3(18), 4.32.4, 5.2 |
| 2315 |
06 |
D-111 |
Public Pay Telephone |
No volume control |
Accessible telephone does not have volume control. |
4.1.3(17)(b) |
| 2316 |
06 |
D-111 |
Public Pay Telephone |
Grasping and twisting |
Push button controls are required: Operable part of
telephone requires grasping or twisting to operate |
4.31.6 |
| 2317 |
06 |
D-111 |
Public Pay Telephone |
12" projection, 28" AFF |
Telephone mounted with bottom between 27" and
80" AFF projects > 4" from the wall or > 12" from a
post. |
4.31.4, 4.4.1; Fig. 8a-e |
| 2318 |
06 |
D-112 |
Collectors Gallery: Wall Mounted Television |
77" AFF, 24" projection |
Protruding object with bottom between 27" and
80" AFF projects more than 4" from wall or 12" from post. |
4.4.1; Fig. 8a-d |
| 2319 |
06 |
D-112 |
Collectors Gallery: Counter |
42" AFF |
Sales, Service or Information Counter(s) or Teller
Window(s) higher than 36" AFF or at Cash Register(s) for sales or
distribution of goods or services to the public. |
7.2 |
| 2320 |
06 |
D-113 |
Visual Alarm in Concourse by Column 12 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2321 |
06 |
D-114 |
Visual Alarm in Concourse by Column 9 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2322 |
06 |
D-115 |
Visual Alarm in Concourse by Column 5 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2323 |
06 |
D-116 |
Fire Pull at Column 12 |
60" AFF |
Control outside reach range. |
4.1.3(13), 4.27.3; Fig. 5, 6 |
| 2324 |
06 |
D-117 |
Fire Pull at Column 6 |
63" AFF |
Control outside reach range. |
4.1.3(13), 4.27.3; Fig. 5, 6 |
| 2356 |
07 |
A-118 |
Men's Toilet Room |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2375 |
07 |
A-119 |
Men's Toilet Room |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2393 |
07 |
A-120 |
Visual Alarm in Concourse by Column 21 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2394 |
07 |
A-121 |
Visual Alarm in Concourse by Column 15 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2445 |
07 |
B-120 |
Visual Alarm in Concourse by Column 34 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2446 |
07 |
B-121 |
Visual Alarm in Concourse by Column 29 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2447 |
07 |
B-122 |
Visual Alarm in Concourse by Column 25 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2480 |
07 |
C-116 |
Men's Toilet Room |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2496 |
07 |
C-117 |
Men's Toilet Room |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2511 |
07 |
C-118 |
Visual Alarm in Concourse by Column 47 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2512 |
07 |
C-119 |
Visual Alarm in Concourse by Column 43 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2513 |
07 |
C-120 |
Visual Alarm in Concourse by Column 40 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2514 |
07 |
C-121 |
Visual Alarm in Concourse by Column 37 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2529 |
07 |
D-108 |
Women's Toilet Room |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2571 |
07 |
D-120 |
Visual Alarm in Concourse by Column 11 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2574 |
07 |
D-123 |
Visual Alarm in Concourse by Column 8 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2575 |
08 |
000 |
Public Pay Telephone |
No forward approach phone |
Two or more banks of public pay telephones on this
floor. None meet the requirements for a forward reach telephone, where a
minimum of 1 per floor is required. |
4.1.3(17)(a) |
| 2577 |
08 |
A-101 |
Lobby Doors |
2 seconds |
Existing Closer causes Door to travel from 70
degrees open to 3" from latch in less than 3 sec. |
4.13.10 |
| 2580 |
08 |
A-102 |
Corridor Ramp |
No handrail |
Ramp > 6" high, or > 72" long with
no handrail or with handrail on one side only. |
4.8.5 |
| 2581 |
08 |
A-103 |
Public Pay Telephone |
No volume control |
Accessible telephone does not have volume control. |
4.1.3(17)(b) |
| 2582 |
08 |
A-103 |
Public Pay Telephone |
Grasping and twisting |
Push button controls are required: Operable part of
telephone requires grasping or twisting to operate |
4.31.6 |
| 2584 |
08 |
A-104 |
Men's Toilet Room |
27.5" clear |
Clear width of active leaf of double door <
32". (Deduct 5/8" from width criteria for Alt. Tech. Infeas.) |
4.13.5; Fig. 24 |
| 2585 |
08 |
A-104 |
Men's Toilet Room |
2.5 seconds |
Existing Closer causes Door to travel from 70
degrees open to 3" from latch in less than 3 sec. |
4.13.10 |
| 2586 |
08 |
A-104 |
Men's Toilet Room |
15# |
Force to operate interior non-fire-rated door
exceeds 5#. |
4.13.11(2)(b) |
| 2587 |
08 |
A-104 |
Men's Toilet Room |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2588 |
08 |
A-104 |
Men's Toilet Room |
No raised lettering and Braille |
Existing room and/or gender identification signage
is noncompliant. |
4.1.3(16)(a), 4.30.4 |
| 2589 |
08 |
A-104 |
Men's Toilet Room |
Sign above door |
Existing room and/or identification sign is
incorrectly located. |
4.30.6 |
| 2591 |
08 |
A-104 |
Men's Toilet Room |
2" rise |
Change in level > .5". |
4.3.8; Fig. 7c, 7d |
| 2592 |
08 |
A-104 |
Men's Toilet Room |
4 stalls, 0 accessible |
No standard accessible toilet stall. If > one
but < six, one standard accessible stall required. |
4.1.3(11), 4.22.4, 4.17.3; Fig. 30a |
| 2593 |
08 |
A-104 |
Men's Toilet Room |
24" clear |
Stall door width < 32" clear width. |
4.1.3(11), 4.22.4, 4.17.5; Fig. 30 |
| 2594 |
08 |
A-104 |
Men's Toilet Room |
No grab bars |
No grab bars. |
4.1.3(11), 4.22.4, 4.16.4, 4.17.6; Fig. 28, 29, 30 |
| 2595 |
08 |
A-104 |
Men's Toilet Room |
16" AFF |
Top of water closet seat <17" or >
19" above finish floor. |
4.1.3(11), 4.22.4, 4.16.3, 4.17.2; Fig. 29b, 30(d) |
| 2596 |
08 |
A-104 |
Men's Toilet Room |
9# |
Manual flush control at water closet requires > 5
lbs. of force to activate. |
4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4 |
| 2597 |
08 |
A-104 |
Men's Toilet Room |
Large roll toilet paper |
Large roll toilet paper dispenser requires pinching
and does not allow continuous delivery. |
4.1.3(11), 4.22.4, 4.16.6, 4.17.2; Fig. 29b, 30(d) |
| 2599 |
08 |
A-104 |
Men's Toilet Room |
11# |
Manual flush control at urinal requires > five
pounds force to activate. |
4.1.3(11), 4.22.5, 4.18.4, 4.27.4 |
| 2600 |
08 |
A-104 |
Men's Toilet Room |
26.5" knee clearance |
Lavatory with < required knee clearance and/or
toe clearance. |
4.1.3(11), 4.22.6, 4.19.2; Fig. 31 |
| 2601 |
08 |
A-104 |
Men's Toilet Room |
11# |
Faucet controls requires > 5 pounds of force to
operate. |
4.1.3(11), 4.22.6, 4.19.5, 4.27.4 |
| 2602 |
08 |
A-104 |
Men's Toilet Room |
46.5" AFF |
Bottom of mirror reflecting surface > 40"
above finish floor. |
4.1.3(11), 4.22.6, 4.19.6; Fig. 31 |
| 2603 |
08 |
A-104 |
Men's Toilet Room |
67" AFF |
Towel dispenser or blower outside reach range. |
4.1.3(11), 4.22.7, 4.27.3; Fig. 4, 5, 6 |
| 2604 |
08 |
A-104 |
Men's Toilet Room |
7# |
Control or operating mechanism takes > 5 lbs.
force to operate or requires tight gripping, grasping or twisting of wrist.
Towel dispenser. |
4.1.3(11), 4.22.7, 4.27.4 |
| 2605 |
08 |
A-104 |
Men's Toilet Room |
14# |
Control or operating mechanism takes > 5 lbs.
force to operate or requires tight gripping, grasping or twisting of wrist.
Soap dispenser. |
4.1.3(11), 4.22.7, 4.27.4 |
| 2606 |
08 |
A-105 |
Public Pay Telephone |
64.25" AFF |
Operable parts of phone outside reach range. |
4.1.3(17), 4.31.3; Fig. 5, 6, 44a-b |
| 2607 |
08 |
A-105 |
Public Pay Telephone |
No volume control |
Accessible telephone does not have volume control. |
4.1.3(17)(b) |
| 2608 |
08 |
A-105 |
Public Pay Telephone |
Grasping and twisting |
Push button controls are required: Operable part of
telephone requires grasping or twisting to operate |
4.31.6 |
| 2609 |
08 |
A-106 |
Door between Concourse and Seating |
Knob |
Existing door hardware requires tight grasping,
pinching, or twisting of the wrist to operate. |
4.13.9 |
| 2610 |
08 |
A-107 |
Visual Alarm in Concourse by Column 21 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2611 |
08 |
A-108 |
Visual Alarm in Concourse by Column 19 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2612 |
08 |
A-109 |
Fire Pull at Column 21 |
63" AFF |
Control outside reach range. |
4.1.3(13), 4.27.3; Fig. 5, 6 |
| 2613 |
08 |
B-101 |
Public Pay Telephone |
Grasping and twisting |
Push button controls are required: Operable part of
telephone requires grasping or twisting to operate |
4.31.6 |
| 2614 |
08 |
B-101 |
Public Pay Telephone |
27.75" AFF, 12" projection |
Telephone mounted with bottom between 27" and
80" AFF projects > 4" from the wall or > 12" from a
post. |
4.31.4, 4.4.1; Fig. 8a-e |
| 2617 |
08 |
B-102 |
Corridor Ramp |
No handrail |
Ramp > 6" high, or > 72" long with
no handrail or with handrail on one side only. |
4.8.5 |
| 2619 |
08 |
B-103 |
Elevator Lobby |
Jamb identification, 1 side only |
Floor Designations at Elevator Hoistway are not
located on both jambs of Hoistway openings. |
4.10.5; Fig. 20 |
| 2621 |
08 |
B-104 |
Lobby Doors |
2 seconds |
Existing Closer causes Door to travel from 70
degrees open to 3" from latch in less than 3 sec. |
4.13.10 |
| 2622 |
08 |
B-105 |
Door between Concourse and Seating at Column 30 |
Knob |
Existing door hardware requires tight grasping,
pinching, or twisting of the wrist to operate. |
4.13.9 |
| 2623 |
08 |
B-106 |
Public Pay Telephones |
64.25" AFF |
Operable parts of phone outside reach range. Two
public pay telephones, none accessible. |
4.1.3(17), 4.31.3; Fig. 5, 6, 44a-b |
| 2624 |
08 |
B-106 |
Public Pay Telephones |
No volume control |
Accessible telephone does not have volume control. |
4.1.3(17)(b) |
| 2625 |
08 |
B-106 |
Public Pay Telephones |
Grasping and twisting |
Push button controls are required: Operable part of
telephone requires grasping or twisting to operate |
4.31.6 |
| 2626 |
08 |
B-107 |
Women's Toilet Room |
27.5" clear |
Clear width of active leaf of double door <
32". (Deduct 5/8" from width criteria for Alt. Tech. Infeas.) |
4.13.5; Fig. 24 |
| 2627 |
08 |
B-107 |
Women's Toilet Room |
21# |
Force to operate interior non-fire-rated door
exceeds 5#. |
4.13.11(2)(b) |
| 2628 |
08 |
B-107 |
Women's Toilet Room |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2629 |
08 |
B-107 |
Women's Toilet Room |
No raised lettering and Braille |
Existing room and/or gender identification signage
is noncompliant. |
4.1.3(16)(a), 4.30.4 |
| 2630 |
08 |
B-107 |
Women's Toilet Room |
Above door |
Existing room and/or identification sign is
incorrectly located. |
4.30.6 |
| 2632 |
08 |
B-107 |
Women's Toilet Room |
10 stalls, 0 ambulatory |
If greater than or equal to 6, and if standard
accessible stall provided, 36" wide ambulatory accessible stall also
required. |
4.1.3(11), 4.22.4; Fig. 30d |
| 2633 |
08 |
B-107 |
Women's Toilet Room |
10 stalls, 0 accessible |
No standard accessible toilet stall. If > one
but < six, one standard accessible stall required. |
4.1.3(11), 4.22.4, 4.17.3; Fig. 30a |
| 2634 |
08 |
B-107 |
Women's Toilet Room |
23.5" clear |
Stall door width < 32" clear width. |
4.1.3(11), 4.22.4, 4.17.5; Fig. 30 |
| 2635 |
08 |
B-107 |
Women's Toilet Room |
15.25" AFF |
Top of water closet seat <17" or >
19" above finish floor. |
4.1.3(11), 4.22.4, 4.16.3, 4.17.2; Fig. 29b, 30(d) |
| 2636 |
08 |
B-107 |
Women's Toilet Room |
15.5" centerline |
Centerline of water closet is < or > 18"
from sidewall or partition. |
4.1.3(11), 4.22.4, 4.16.2, 4.17.3; Fig. 28, 30 |
| 2637 |
08 |
B-107 |
Women's Toilet Room |
12# |
Manual flush control at water closet requires > 5
lbs. of force to activate. |
4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4 |
| 2638 |
08 |
B-107 |
Women's Toilet Room |
Large roll toilet paper |
Large roll toilet paper dispenser requires pinching
and does not allow continuous delivery. |
4.1.3(11), 4.22.4, 4.16.6, 4.17.2; Fig. 29b, 30(d) |
| 2640 |
08 |
B-107 |
Women's Toilet Room |
No insulation |
Hot water pipes not insulated or covered. |
4.1.3(11), 4.22.6, 4.19.4 |
| 2641 |
08 |
B-107 |
Women's Toilet Room |
7 seconds |
Self-closing faucet < 10 seconds open. |
4.1.3(11), 4.22.6, 4.19.5 |
| 2642 |
08 |
B-107 |
Women's Toilet Room |
7# |
Faucet controls requires > 5 pounds of force to
operate. |
4.1.3(11), 4.22.6, 4.19.5, 4.27.4 |
| 2643 |
08 |
B-107 |
Women's Toilet Room |
46" AFF |
Bottom of mirror reflecting surface > 40"
above finish floor. |
4.1.3(11), 4.22.6, 4.19.6; Fig. 31 |
| 2644 |
08 |
B-107 |
Women's Toilet Room |
66.75" AFF |
Towel dispenser or blower outside reach range. |
4.1.3(11), 4.22.7, 4.27.3; Fig. 4, 5, 6 |
| 2645 |
08 |
B-107 |
Women's Toilet Room |
15# |
Control or operating mechanism takes > 5 lbs.
force to operate or requires tight gripping, grasping or twisting of wrist.
Soap dispenser. |
4.1.3(11), 4.22.7, 4.27.4 |
| 2650 |
08 |
B-109 |
Visual Alarm in Concourse by Column 30 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2651 |
08 |
B-110 |
Visual Alarm in Concourse by Column 26 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2652 |
08 |
B-111 |
Visual Alarm in Concourse by Column 25 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2653 |
08 |
B-112 |
Fire Pull at Column 25 |
63" AFF |
Control outside reach range. |
4.1.3(13), 4.27.3; Fig. 5, 6 |
| 2654 |
08 |
B-113 |
Fire Pull at Column 30 |
63" AFF |
Control outside reach range. |
4.1.3(13), 4.27.3; Fig. 5, 6 |
| 2655 |
08 |
C-101 |
Men's Toilet Room |
27.5" clear |
Clear width of active leaf of double door <
32". (Deduct 5/8" from width criteria for Alt. Tech. Infeas.) |
4.13.5; Fig. 24 |
| 2656 |
08 |
C-101 |
Men's Toilet Room |
2 seconds |
Existing Closer causes Door to travel from 70
degrees open to 3" from latch in less than 3 sec. |
4.13.10 |
| 2657 |
08 |
C-101 |
Men's Toilet Room |
12# |
Force to operate interior non-fire-rated door
exceeds 5#. |
4.13.11(2)(b) |
| 2658 |
08 |
C-101 |
Men's Toilet Room |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2659 |
08 |
C-101 |
Men's Toilet Room |
No raised lettering and Braille |
Existing room and/or gender identification signage
is noncompliant. |
4.1.3(16)(a), 4.30.4 |
| 2660 |
08 |
C-101 |
Men's Toilet Room |
Sign above door |
Existing room and/or identification sign is
incorrectly located. |
4.30.6 |
| 2662 |
08 |
C-101 |
Men's Toilet Room |
.75" AFF |
Change in level > .5". Marble threshold. |
4.3.8; Fig. 7c, 7d |
| 2663 |
08 |
C-101 |
Men's Toilet Room |
4 stalls, 0 accessible |
No standard accessible toilet stall. If > one
but < six, one standard accessible stall required. |
4.1.3(11), 4.22.4, 4.17.3; Fig. 30a |
| 2664 |
08 |
C-101 |
Men's Toilet Room |
24" clear |
Stall door width < 32" clear width. |
4.1.3(11), 4.22.4, 4.17.5; Fig. 30 |
| 2665 |
08 |
C-101 |
Men's Toilet Room |
65.5" AFF |
Coat hook > 48" above finish floor front
reach, or > 54"; side reach. |
4.22.7, 4.27.3; Fig. 5, 6 |
| 2666 |
08 |
C-101 |
Men's Toilet Room |
16" AFF |
Top of water closet seat <17" or >
19" above finish floor. |
4.1.3(11), 4.22.4, 4.16.3, 4.17.2; Fig. 29b, 30(d) |
| 2667 |
08 |
C-101 |
Men's Toilet Room |
15" centerline |
Centerline of water closet is < or > 18"
from sidewall or partition. |
4.1.3(11), 4.22.4, 4.16.2, 4.17.3; Fig. 28, 30 |
| 2669 |
08 |
C-101 |
Men's Toilet Room |
8# |
Manual flush control at water closet requires > 5
lbs. of force to activate. |
4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4 |
| 2670 |
08 |
C-101 |
Men's Toilet Room |
9# |
Manual flush control at water closet requires > 5
lbs. of force to activate. |
4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4 |
| 2672 |
08 |
C-101 |
Men's Toilet Room |
Not insulated |
Hot water pipes not insulated or covered. |
4.1.3(11), 4.22.6, 4.19.4 |
| 2673 |
08 |
C-101 |
Men's Toilet Room |
10# |
Faucet controls requires > 5 pounds of force to
operate. |
4.1.3(11), 4.22.6, 4.19.5, 4.27.4 |
| 2674 |
08 |
C-101 |
Men's Toilet Room |
46.25" AFF |
Bottom of mirror reflecting surface > 40"
above finish floor. |
4.1.3(11), 4.22.6, 4.19.6; Fig. 31 |
| 2675 |
08 |
C-101 |
Men's Toilet Room |
67.25" AFF |
Towel dispenser or blower outside reach range. |
4.1.3(11), 4.22.7, 4.27.3; Fig. 4, 5, 6 |
| 2676 |
08 |
C-101 |
Men's Toilet Room |
14# |
Control or operating mechanism takes > 5 lbs.
force to operate or requires tight gripping, grasping or twisting of wrist.
Soap dispenser. |
4.1.3(11), 4.22.7, 4.27.4 |
| 2679 |
08 |
C-102 |
Corridor Ramp |
No handrail |
Ramp > 6" high, or > 72" long with
no handrail or with handrail on one side only. |
4.8.5 |
| 2680 |
08 |
C-103 |
Public Pay Telephone |
64" AFF |
Operable parts of phone outside reach range. Two
pay telephones, none accessible. |
4.1.3(17), 4.31.3; Fig. 5, 6, 44a-b |
| 2681 |
08 |
C-103 |
Public Pay Telephone |
No volume control |
Accessible telephone does not have volume control. |
4.1.3(17)(b) |
| 2682 |
08 |
C-103 |
Public Pay Telephone |
Grasping and twisting |
Push button controls are required: Operable part of
telephone requires grasping or twisting to operate |
4.31.6 |
| 2686 |
08 |
C-106 |
Public Pay Telephone |
No volume control |
Accessible telephone does not have volume control. |
4.1.3(17)(b) |
| 2687 |
08 |
C-106 |
Public Pay Telephone |
Grasping and twisting |
Push button controls are required: Operable part of
telephone requires grasping or twisting to operate |
4.31.6 |
| 2692 |
08 |
C-108 |
Visual Alarm in Concourse by Column 1 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2693 |
08 |
C-109 |
Visual Alarm in Concourse by Column 47 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2694 |
08 |
C-110 |
Visual Alarm in Concourse by Column 44 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2695 |
08 |
C-111 |
Fire Pull at Column 43 |
62.5" AFF |
Control outside reach range. |
4.1.3(13), 4.27.3; Fig. 5, 6 |
| 2696 |
08 |
C-112 |
Fire Pull at Column 1 |
64" AFF |
Control outside reach range. |
4.1.3(13), 4.27.3; Fig. 5, 6 |
| 2698 |
08 |
D-102 |
Public Pay Telephone |
64" AFF |
Operable parts of phone outside reach range. Two
pay phones, none accessible. |
4.1.3(17), 4.31.3; Fig. 5, 6, 44a-b |
| 2699 |
08 |
D-102 |
Public Pay Telephone |
No volume control |
Accessible telephone does not have volume control. |
4.1.3(17)(b) |
| 2700 |
08 |
D-102 |
Public Pay Telephone |
Grasping and twisting |
Push button controls are required: Operable part of
telephone requires grasping or twisting to operate |
4.31.6 |
| 2703 |
08 |
D-103 |
Corridor Ramp |
No handrail |
Ramp > 6" high, or > 72" long with
no handrail or with handrail on one side only. |
4.8.5 |
| 2704 |
08 |
D-104 |
Women's Toilet Room |
27.5" clear |
Clear width of active leaf of double door <
32". (Deduct 5/8" from width criteria for Alt. Tech. Infeas.) |
4.13.5; Fig. 24 |
| 2705 |
08 |
D-104 |
Women's Toilet Room |
.75" abrupt |
Existing beveled threshold is greater than 3/4"
high, or greater than 3/4" high at Exterior Sliding Door. Threshold at
entrance to toilet room. |
4.1.6(3)(d)(ii), 4.13.8; Fig. 7c, 7d |
| 2706 |
08 |
D-104 |
Women's Toilet Room |
12# |
Force to operate interior non-fire-rated door
exceeds 5#. |
4.13.11(2)(b) |
| 2707 |
08 |
D-104 |
Women's Toilet Room |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2708 |
08 |
D-104 |
Women's Toilet Room |
No raised lettering and Braille |
Existing room and/or gender identification signage
is noncompliant. |
4.1.3(16)(a), 4.30.4 |
| 2709 |
08 |
D-104 |
Women's Toilet Room |
Sign above door. |
Existing room and/or identification sign is
incorrectly located. |
4.30.6 |
| 2711 |
08 |
D-104 |
Women's Toilet Room |
10 stalls, 0 ambulatory |
If greater than or equal to 6, and if standard
accessible stall provided, 36" wide ambulatory accessible stall also
required. |
4.1.3(11), 4.22.4; Fig. 30d |
| 2712 |
08 |
D-104 |
Women's Toilet Room |
10 stalls, 0 accessible |
No standard accessible toilet stall. If > one
but < six, one standard accessible stall required. |
4.1.3(11), 4.22.4, 4.17.3; Fig. 30a |
| 2713 |
08 |
D-104 |
Women's Toilet Room |
23.25" clear |
Stall door width < 32" clear width. |
4.1.3(11), 4.22.4, 4.17.5; Fig. 30 |
| 2714 |
08 |
D-104 |
Women's Toilet Room |
67" AFF |
Coat hook > 48" above finish floor front
reach, or > 54"; side reach. |
4.22.7, 4.27.3; Fig. 5, 6 |
| 2715 |
08 |
D-104 |
Women's Toilet Room |
No grab bars |
No grab bars. |
4.1.3(11), 4.22.4, 4.16.4, 4.17.6; Fig. 28, 29, 30 |
| 2716 |
08 |
D-104 |
Women's Toilet Room |
16" AFF |
Top of water closet seat <17" or >
19" above finish floor. |
4.1.3(11), 4.22.4, 4.16.3, 4.17.2; Fig. 29b, 30(d) |
| 2717 |
08 |
D-104 |
Women's Toilet Room |
14.25" centerline |
Centerline of water closet is < or > 18"
from sidewall or partition. |
4.1.3(11), 4.22.4, 4.16.2, 4.17.3; Fig. 28, 30 |
| 2718 |
08 |
D-104 |
Women's Toilet Room |
9# |
Manual flush control at water closet requires > 5
lbs. of force to activate. |
4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4 |
| 2719 |
08 |
D-104 |
Women's Toilet Room |
Large roll toilet paper |
Large roll toilet paper dispenser requires pinching
and does not allow continuous delivery. |
4.1.3(11), 4.22.4, 4.16.6, 4.17.2; Fig. 29b, 30(d) |
| 2721 |
08 |
D-104 |
Women's Toilet Room |
No insulation |
Hot water pipes not insulated or covered. |
4.1.3(11), 4.22.6, 4.19.4 |
| 2722 |
08 |
D-104 |
Women's Toilet Room |
5 seconds |
Self-closing faucet < 10 seconds open. |
4.1.3(11), 4.22.6, 4.19.5 |
| 2723 |
08 |
D-104 |
Women's Toilet Room |
46.5" AFF |
Bottom of mirror reflecting surface > 40"
above finish floor. |
4.1.3(11), 4.22.6, 4.19.6; Fig. 31 |
| 2724 |
08 |
D-104 |
Women's Toilet Room |
67.5" AFF |
Towel dispenser or blower outside reach range. |
4.1.3(11), 4.22.7, 4.27.3; Fig. 4, 5, 6 |
| 2725 |
08 |
D-104 |
Women's Toilet Room |
15# |
Control or operating mechanism takes > 5 lbs.
force to operate or requires tight gripping, grasping or twisting of wrist.
Soap dispenser. |
4.1.3(11), 4.22.7, 4.27.4 |
| 2726 |
08 |
D-105 |
Public Pay Telephone |
No volume control |
Accessible telephone does not have volume control. |
4.1.3(17)(b) |
| 2727 |
08 |
D-105 |
Public Pay Telephone |
Grasping and twisting |
Push button controls are required: Operable part of
telephone requires grasping or twisting to operate |
4.31.6 |
| 2728 |
08 |
D-106 |
Visual Alarm in Concourse by Column 6 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2729 |
08 |
D-107 |
Visual Alarm in Concourse by Column 3 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2730 |
08 |
D-108 |
Fire Pull at Column 6 |
64.5" AFF |
Control outside reach range. |
4.1.3(13), 4.27.3; Fig. 5, 6 |
| 2731 |
09 |
000 |
Public Pay Telephone |
No forward approach phone |
Two or more banks of public pay telephones on this
floor. None meet the requirements for a forward reach telephone, where a
minimum of 1 per floor is required. |
4.1.3(17)(a) |
| 2753 |
09 |
A-110 |
Visual Alarm in Corridor by Column 16 |
76" AFF, 9.75" from ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2757 |
09 |
B-102 |
Men's Toilet Room |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2758 |
09 |
B-102 |
Men's Toilet Room |
No raised lettering and Braille |
Existing room and/or gender identification signage
is noncompliant. |
4.1.3(16)(a), 4.30.4 |
| 2759 |
09 |
B-102 |
Men's Toilet Room |
Not on latch side |
Existing room and/or identification sign is
incorrectly located. |
4.30.6 |
| 2760 |
09 |
B-102 |
Men's Toilet Room |
Inaccessible; no directional signage |
No directional signage to nearest accessible toilet
room at inaccessible toilet room. |
4.1.6(3)(e)(iii) |
| 2779 |
09 |
B-103 |
Women's Toilet Room |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2780 |
09 |
B-103 |
Women's Toilet Room |
No raised lettering and Braille |
Existing room and/or gender identification signage
is noncompliant. |
4.1.3(16)(a), 4.30.4 |
| 2781 |
09 |
B-103 |
Women's Toilet Room |
Not on latch side |
Existing room and/or identification sign is
incorrectly located. |
4.30.6 |
| 2782 |
09 |
B-103 |
Women's Toilet Room |
Inaccessible; no directional signage |
No directional signage to nearest accessible toilet
room at inaccessible toilet room. |
4.1.6(3)(e)(iii) |
| 2844 |
09 |
C-106 |
Men's Toilet Room |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2845 |
09 |
C-106 |
Men's Toilet Room |
No raised lettering and Braille |
Existing room and/or gender identification signage
is noncompliant. |
4.1.3(16)(a), 4.30.4 |
| 2846 |
09 |
C-106 |
Men's Toilet Room |
Not on latch side |
Existing room and/or identification sign is
incorrectly located. |
4.30.6 |
| 2847 |
09 |
C-106 |
Men's Toilet Room |
Inaccessible; no directional signage |
No directional signage to nearest accessible toilet
room at inaccessible toilet room. |
4.1.6(3)(e)(iii) |
| 2868 |
09 |
C-107 |
Concession Counter; Slope Along Accessible Route |
14.60% |
Excessive slope without handrails along accessible
route |
4.3.7, 4.5.2 |
| 2869 |
09 |
C-107 |
Condiment Counter |
32" AFF, 15" projection |
Protruding object with bottom between 27" and
80" AFF projects more than 4" from wall or 12" from post. |
4.4.1; Fig. 8a-d |
| 2871 |
09 |
C-107 |
Concession Counter |
40.75" AFF |
Sales, Service or Information Counter(s) or Teller
Window(s) higher than 36" AFF or at Cash Register(s) for sales or
distribution of goods or services to the public. |
7.2 |
| 2872 |
09 |
C-108 |
Women's Toilet Room |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2873 |
09 |
C-108 |
Women's Toilet Room |
No raised lettering and Braille |
Existing room and/or gender identification signage
is noncompliant. |
4.1.3(16)(a), 4.30.4 |
| 2874 |
09 |
C-108 |
Women's Toilet Room |
Not on latch side |
Existing room and/or identification sign is
incorrectly located. |
4.30.6 |
| 2875 |
09 |
C-108 |
Women's Toilet Room |
No directional signage |
No directional signage to nearest accessible toilet
room at inaccessible toilet room. |
4.1.6(3)(e)(iii) |
| 2934 |
09 |
D-111 |
Visual Alarm in Concourse by Column 10 |
75.75" AFF, 10.5" from ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2982 |
10 |
A-110 |
Visual Alarm in Concourse by Column 18 |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2983 |
10 |
A-111 |
Visual Alarm in Concourse by Column |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). |
4.28.3(6) |
| 2984 |
10 |
A-112 |
Visual Alarm in Concourse by Column |
Visual alarm on ceiling |
Visual Signal(s) mounted at incorrect height.
Visual signal is to be mounted at 80" AFF or 6" below ceiling
(whichever is lower). | 4.28.3(6) |