Attachment K: Program Access in Existing Facilities
Please Note: Paragraph 31 of the Settlement Agreement requires that within three months of the effective date of this Agreement, the City provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible.
In order to ensure that each of the City’s programs, services, and activities operating at a facility that is the subject of this Agreement, when viewed in its entirety, are readily accessible to and usable by persons with disabilities, the City will take the following actions:
1. By December 31, 2010, the City will complete the following modifications to the Police Department Headquarters, located at 505 S. 15th Street:
a. First Floor Drinking Fountains: Due to the alcove, access for a parallel approach is diminished and no forward approach is available. Provide a lower drinking fountain that complies with the Standards and that is accompanied by a 30 inch by 48 inch clear floor space and an adequate route to the clear floor space to enable persons with wheelchairs to approach and use the fountain. Standards §§ 4.15, 4.27.4, Fig. 27.
b. Main Entrance
i. The pull/latch side of the hinged door has a maneuvering clearance of only 6 inches. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards § 4.13.6, Fig. 25(a).
ii. The threshold has a vertical rise of 1 ½ inches and is not beveled. Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2. Standards §§ 4.13.8, 4.5.2.
c. Alarms: There are audible alarms but no visible alarms in hallways, corridors, meeting rooms, toilet rooms, or lobby. Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use. Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate. Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower. Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal. In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling. Standards § 4.28.3.
d. Elevator
i. The door stays open for only 8 seconds after reopening in response to an obstruction. Provide doors that open and close automatically with a reopening device that will stop and reopen the car door and hoistway door automatically if the door becomes obstructed by an object or person. Ensure that the device is capable of completing these operations without requiring contact for obstructions passing through the opening at heights of 5 inches and 29 inches above the finished floor; that door reopening devices remain effective for at least 20 seconds, after which the doors may close; that the minimum time from notification that a car is answering a call until the doors of that car start to close is 5 seconds; and that the minimum time for elevator doors to remain fully open in response to a car call is 3 seconds. Standards §§ 4.10.6, 4.10.7, 4.10.8, Figs. 20, 21.
e. Fifth Floor Drinking Fountains: There are two drinking fountains, but none is lower enough to be accessible to persons who use wheelchairs. Provide at least one cup dispenser and cups on an accessible route and within accessible reach ranges. Ensure that fountain controls are operable with one hand, require 5 lbf or less to operate without tight grasping, pinching, or twisting of the wrist; and are front mounted or side mounted near the front edge. Additionally, provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a “hi-lo” fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser; or by such other means as would achieve the required accessibility for each group of people. Standards §§ 4.15, 4.27.4, Fig. 27.
f. Fifth Floor Men’s and Women’s Single User Toilet Rooms (altered element). For each gender (or as a unisex toilet room), make the following modifications:
i. The room sign is centered at 54 inches above the finished floor. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
iii. Women’s Only: No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.
iv. The toilet’s flush control mechanism is on the closed side. Provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.27.4.
v. The far end of the side portion of the continuous grab bar measures only 50 inches from the rear wall and the far end of the rear portion measures only 34-1/2 inches from the side wall. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall, and a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Ensure that the grab bars are mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bars and the wall; and at least 1½ inches between the grab bars and any other object, such as a toilet paper dispenser or a toilet seat cover dispenser. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, 4.26.2, Fig. 29.
vi. Men’s Only: The door swings into the required clear floor space at the lavatory. Ensure that no door swings into the required clear floor space at any accessible fixture. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.2.
g. First Floor Unisex Single User Toilet Rooms, Right and Left. These have the same barriers; the City will make the following modifications at one:
i. There is no accessible door signage identifying this room as an accessible toilet room. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The door swings into the clear floor space required at the lavatory and the toilet. Ensure that no door swings into the required clear floor space at any accessible fixture. Standards § 4.22.2.
iii. No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
iv. There is insufficient turning space within the toilet room. Provide an unobstructed turning space at least 60 inches in diameter or a T-shaped space complying with Fig. 3(b). Standards §§ 4.22.3, 4.2.3, Fig. 3.
v. The toilet centerline measures 19 ½ inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards § 4.16.2, Fig. 28.
vi. The far end of the side grab bar is 52 inches from the rear wall. Provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards § 4.16.4, Fig. 29(b).
h. Jail: Although one of the cells has a combination lavatory/toilet fixture with a side grab bar, none of the cells is fully accessible to persons with disabilities. Additionally, there is no accessible shower or bathing facility available to inmates with disabilities. Provide a fully accessible holding cell AND a showering or bathing facility for inmates with disabilities that complies with the Standards, or implement written procedures to hold inmates with disabilities at an alternative fully-accessible location. If an alternate location is selected, submit the written procedures to the Department for prior approval.
2. By December 31, 2008, the City will complete the following modifications to the OmahaPark Three, located at 828 Farnam:
a. Parking: (*City will determine whether van accessible height allowances would risk the integrity of the building). Out of 83 total spaces, there are 4 standard spaces designated as reserved for persons with disabilities. No space is currently designated as “van accessible.” Two of the designated spaces are narrower than 96 inches. The two other designated spaces have excessive slopes and cross-slopes in their spaces and access aisles. The vertical clearance in the garage is only 7 feet. The designated spaces’ vertical signage can be obstructed by parked vehicles. On the shortest accessible route to the accessible entrance, provide 1 van accessible space and 3 standard spaces designated as reserved for people with disabilities. Ensure that standard accessible spaces are a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional “Van-Accessible” sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
b. Ramp from Rooftop Parking to Gene Leahy Mall: The handrails measure 32 and 41-½ inches above the finished floor; there are inadequate handrail extensions at the top of the ramp; and there is 6 1/4 inches between the handrail and the wall. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Standards § 4.8.5.
3. By December 31, 2009, the City will complete the following modifications to the Swanson Library, located at 9101 W. Dodge Road:
a. Parking (Upper Lot): Of the 36 total parking spaces provided, 2 are standard spaces designated as reserved for persons with disabilities. There is no space served by a 96 inch wide access aisle, nor is there a sign designating a space as “van-accessible.” Both of the spaces designated for persons with disabilities are narrower than 96 inches and neither spaces nor access aisles are level. On the shortest accessible route to the accessible entrance, provide 1 van accessible space and 1 standard space designated as reserved for people with disabilities. Ensure that standard accessible spaces are a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional “Van-Accessible” sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
b. Alarms: There are audible alarms but no visual in hallways, corridors, meeting rooms, toilet rooms, and lobbies. Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use. Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate. Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower. Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal. In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling. Standards § 4.28.3.
c. Elevator
i. After reopening in response to an obstruction, the doors stay open for only 2 seconds. Provide doors that open and close automatically with a reopening device that will stop and reopen the car door and hoistway door automatically if the door becomes obstructed by an object or person. Ensure that the device is capable of completing these operations without requiring contact for obstructions passing through the opening at heights of 5 inches and 29 inches above the finished floor; that door reopening devices remain effective for at least 20 seconds, after which the doors may close; that the minimum time from notification that a car is answering a call until the doors of that car start to close is 5 seconds; and that the minimum time for elevator doors to remain fully open in response to a car call is 3 seconds. Standards §§ 4.10.6, 4.10.7, 4.10.8, Figs. 20, 21.
ii. The emergency controls not grouped at bottom of panel. Provide emergency controls, including the emergency alarm and emergency stop, grouped at the bottom of the panel with their centerlines no less than 35 inches above the finished floor. Standards § 4.10.12, Fig. 23.
iii. The emergency communications system will not work without voice communication; a test call revealed that the operator could not determine the location of the caller unless the caller so informed him or her. Provide a two-way communication system such that it does not require voice communication, the highest operable part is a maximum of 48 inches above the finished floor of the car, and it is identified by a raised symbol and lettering located adjacent to the device. If the system uses a handset, ensure that the length of the cord from the panel to the handset is at least 29 inches. If the system is located in a closed compartment, ensure that the compartment door hardware operates without tight grasping, pinching or twisting of the wrist. Standards § 4.10.14.
d. Drinking Fountain - Lower Level: Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. Provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a “hi-lo” fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards § 4.1.3(10)(a).
e. Men’s and Women’s Single User Toilet Rooms - Lower Level. For each (or as a unisex toilet room, with directional signage at the inaccessible toilet room):
i. The sign is mounted on door, with a centerline at 52 inches above the finished floor. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The door requires 10-15 pounds of force to operate. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).
iii. The door swings into the clear floor space required at the lavatory. Ensure that no door swings into the required clear floor space at any accessible fixture. Standards § 4.22.2.
iv. Men’s Only: No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards § 4.19.6.
v. Men’s Only: The centerline of the toilet is 17 inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards § 4.16.2, Fig. 28.
vi. The toilet paper dispenser is centered 41 inches from the rear wall. Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor. Standards § 4.16.6, Fig. 29(b).
vii. Women’s Only: The bottom edge of the lavatory apron is 28 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards § 4.19.2, Fig. 31.
viii. Women’s Only: The toilet flush control is on the closed side. Provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.16.5, 4.27.4.
4. By December 31, 2010, the City will complete the following modifications to the A. V. Sorenson Community Center and Library, located at 4804 Cass Street:
a. A.V. Sorenson Center Parking Lot: Although 2 of the 8 parking spaces are designated as reserved for persons with disabilities, one of the access aisles has a built-up curb ramp encroaching into it. Provide a curb ramp located so that it does not project into this element and all aspects of the ramp or curb cut comply with the Standards. Standards §§ 4.3.8, 4.7.6.
b. Entrance: The front entrance door has an opening width of only 31 inches. Provide a designated accessible entrance with a clear opening of 32 inches with the door open 90 degrees, measured between the face of the door and the opposite stop. Standards § 4.13.5, Fig. 24.
c. Permanent Room Signs: All rooms lack raised and Braille signs, mounted at 60 inches above the finished floor on the wall to the latch side of the door, with the correct character height. Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door. Standards §§ 4.30.1, 4.30.4, 4.30.5, 4.30.6.
d. Telephone
i. Although one telephone is provided, it is not low enough to be used by persons who use wheelchairs. Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; that is hearing aid compatible and has a volume control mechanism; with telephone books, if provided, located between 15 and 48 inches above the finished floor for a front approach or between 9 and 54 inches above the finished floor for a side approach; with a cord of at least 29 inches long from the telephone to the handset; and with signage that complies with the Standards. Standards §§ 4.31, 4.30.7(2).
ii. No TTY is provided. Provide at least one accessible public TTY with appropriate signage. Standards §§ 4.30.7(3), 4.31.9.
iii. The telephone is a protruding object that is not cane-detectable. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.
e. A.V. Sorenson Center Weight Room
i. The door requires 10 pounds of force to operate. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).
ii. There is no accessible route to and around the weight equipment. Provide at least one accessible route connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide. Standards §§ 4.3, 4.5, Fig. 7.
f. A.V. Sorenson Center Men’s and Women’s Toilet Rooms with Stalls at Front Entrance. For each:
i. Women’s Only: The toilet room sign is not mounted on the wall to the latch side of the door. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The door requires 8 pounds of force to operate. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).
iii. There is only 42 inches of width on the pull/ latch side of the door, which requires a latch-side approach. On the pull side of the door, provide a path of travel at least 48 inches wide for a side approach and at least 24 inches of clear maneuvering space adjacent to the latch side of the door. Standards § 4.13.6, Fig. 25©.
iv. Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.28.1, 4.28.3.
v. The air dryer is a protruding object that is not cane-detectable. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.
vi. Women’s Only: The bottom edge of the lavatory apron is 27-1/2 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards § 4.19.2, Fig. 31.
vii. Women’s Only: The toilet centerline measures 19 inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards § 4.16.2, Fig. 28.
viii. Women’s Only: The toilet flush control is on the closed side. Provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.16.5, 4.27.4.
ix. No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
x. There is 2-3/4 inches between the toilet’s side grab bar and the side wall. Provide grab bars such that there is 1½ inches between the grab bar and the wall. Standards § 4.26.2, Fig. 39.
xi. Men’s Only: There is insufficient turning space within the toilet room. Provide an unobstructed turning space at least 60 inches in diameter or a T-shaped space complying with Fig. 3(b). Standards §§ 4.22.3, 4.2.3, Fig. 3.
xii. Men’s Only: The soap dispenser is mounted with the controls at 51 inches and requiring a forward reach. Provide a soap dispenser such that the controls comply with Fig. 5 for a forward reach or with Fig. 6 for a side reach and such that it is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach, respectively, by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
g. A.V. Sorenson Center Men’s and Women’s Toilet Rooms at Meeting Room. For each:
i. There is no accessible room signage. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The toilet room door swings into the required clear floor space at the lavatory. Ensure that no door swings into the required clear floor space at any accessible fixture. Standards § 4.22.2.
iii. Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.28.1, 4.28.3.
iv. There is insufficient turning space within the toilet room. Provide an unobstructed turning space at least 60 inches in diameter or a T-shaped space complying with Fig. 3(b). Standards §§ 4.22.3, 4.2.3, Fig. 3.
v. Men’s Only: The air dryer is a protruding object that is not cane-detectable. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.
vi. There is no accessible toilet stall provided. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, coat hook, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
h. A.V. Sorenson Center Offices: The Library Office counter is 40 inches above the finished floor. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.
i. A.V. Sorenson Library Entrance Elevator
i. After reopening in response to an obstruction, the door stays open only 9 seconds. Provide doors that open and close automatically with a reopening device that will stop and reopen the car door and hoistway door automatically if the door becomes obstructed by an object or person. Ensure that the device is capable of completing these operations without requiring contact for obstructions passing through the opening at heights of 5 inches and 29 inches above the finished floor; that door reopening devices remain effective for at least 20 seconds, after which the doors may close; that the minimum time from notification that a car is answering a call until the doors of that car start to close is 5 seconds; and that the minimum time for elevator doors to remain fully open in response to a car call is 3 seconds. Standards §§ 4.10.6, 4.10.7, 4.10.8, Figs. 20, 21.
ii. The emergency communications system will not work without voice communication. Provide a two-way communication system such that it does not require voice communication, the highest operable part is a maximum of 48 inches above the finished floor of the car, and it is identified by a raised symbol and lettering located adjacent to the device. If the system uses a handset, ensure that the length of the cord from the panel to the handset is at least 29 inches. If the system is located in a closed compartment, ensure that the compartment door hardware operates without tight grasping, pinching or twisting of the wrist. Standards § 4.10.14.
j. First Floor Drinking Fountains near Entrance: The high drinking fountain is a protruding object that is not cane-detectable. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.
k. First Floor Drinking Fountain at Meeting Room: The water height is only 2-1/2 inches. Provide at least one drinking fountain with a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet; and a spout located at the front of the unit that directs the water flow in a trajectory that is nearly parallel to the front of the unit and is positioned so the flow of water is within 3 inches of the front edge of the fountain and at least 4 inches high. Standards §§ 4.15, 4.27.4, Fig. 27.
l. First Floor Drinking Fountain at Gym
i. The drinking fountain has a spout height of 40 ½ inches above the finished floor; the water height is less than 4 inches, and there is inadequate knee space to enable a front approach. Provide at least one drinking fountain with a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet; and a spout located at the front of the unit that directs the water flow in a trajectory that is nearly parallel to the front of the unit and is positioned so the flow of water is within 3 inches of the front edge of the fountain and at least 4 inches high. Standards §§ 4.15, 4.27.4, Fig. 27. Alternatively, provide a cup dispenser and cups on an accessible route and within accessible reach ranges.
ii. The drinking fountain is a protruding object that is not cane-detectable. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.
m. Second Floor Drinking Fountains at Library: The high/low drinking fountain is a protruding object that is not cane-detectable. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.
n. Men’s and Women’s Toilet Rooms with Stalls near Gym. For each:
i. There is no accessible toilet room sign. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The door requires 12 pounds of force to operate. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).
iii. Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.28.1, 4.28.3.
iv. The air dryer is a protruding object that is not cane-detectable. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.
v. The bottom edge of the lavatory apron is 23-1/2 inches above the finished floor, there is inadequate knee and toe clearance, there is inadequate clear floor space in front of the lavatory, and the lavatory hardware is a twist-style knob that requires tight grasping, pinching, or twisting of the wrist. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; knee and toe clearances that comply with Fig. 31; hot water and drain pipes covered or otherwise configured to protect against contact; clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory; and a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.2, 4.19.3, 4.19.4, 4.19.5, 4.27.4, Figs. 31, 32.
vi. The only toilet stall is not accessible to persons who use wheelchairs, as it is a narrow stall with parallel grab bars. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
vii. “Alternate” configuration toilet stall: The toilet paper dispenser is mounted above the grab bar; the grab bars are not long enough and are mounted too low; and the space between the grab bar and the wall is 3 inches. Provide at least one stall that is exactly 36 inches wide with a toilet 18 inches from each wall or partition, an outward swinging, self-closing door, and parallel grab bars complying with Fig 30(d). Standards §§ 4.22.4, Fig. 30(d).
viii. Men’s Only: There is inadequate maneuvering space on the push side of the door, which requires a forward approach and has both a closer and a latch. On the push side of the door, provide maneuvering clearance at least 48 inches deep and provide a minimum of 12 inches of maneuvering clearance on the latch side of the door, or remove the closer or the latch. Standards § 4.13.6, Fig. 25(a).
o. Women’s and Men’s Toilet Rooms - 2nd Floor near Library. For each:
i. The door requires 9-10 pounds of force to operate. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).
ii. Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.28.1, 4.28.3.
iii. There is inadequate turning space within the room. Provide an unobstructed turning space at least 60 inches in diameter or a T-shaped space complying with Fig. 3(b). Standards §§ 4.22.3, 4.2.3, Fig. 3.
iv. The air dryer is a protruding object that is not cane-detectable. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.
v. Women’s Only: The bottom edge of the lavatory apron is 27 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards § 4.19.2, Fig. 31.
vi. Toilet Stall for Persons with Disabilities
(1) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(2) There is 2-3/4 inches between the side grab bar and the side wall. Provide grab bars such that there is 1½ inches between the grab bar and the wall. Standards § 4.26.2, Fig. 39.
(3) Women’s Only: The toilet centerline is 19 inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards § 4.17.3, Fig. 30.Center line 19
(4) Women’s Only: The toilet flush control is on the closed side. Provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.16.5, 4.17.2, 4.27.4.
5. By December 31, 2011, the City will complete the following modifications to the Sherman Community Center, located at 5701 N. 16th Street:
a. Parking: Although 1 of the 20 spaces is designated as reserved for persons with disabilities, there is no “van-accessible” space. On the shortest accessible route to the accessible entrance, provide 1 van accessible space designated as reserved for people with disabilities. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional “Van-Accessible” sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
b. Exterior Entrance
i. The threshold is ½ inch high and is not beveled. Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2. Standards §§ 4.13.8, 4.5.2.
ii. The interior door requires 10 pounds of force to operate. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).
iii. The coat racks in the hallway are protruding objects that are not cane-detectable. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.
c. Telephones: Although a public telephone is provided, there is no TTY available. Provide at least one accessible public TTY with appropriate signage. Standards §§ 4.30.7(3), 4.31.9.
d. Door Knobs: Throughout the building, the door have round doorknobs. Throughout all areas where the public has access, provide doors with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards § 4.13.9.
e. Counters: The counters in the recreation room and the lobby are 42-1/2 inches above the finished floor. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor. Standards §§ 7.2(1), 4.3.
f. Gymnasium: The gym has 2 entrances, only one of which is accessible. As a program access solution, provide signage at the inaccessible entrance (the 29-1/2 inch wide doorway) directing users with disabilities to the other entrance (the double doors). Standards §§ 4.1.3(8)(d), 4.13, 4.30.
g. Recreation Room Men’s and Women’s Toilet Rooms with Stalls (altered elements; alterations standards apply). For each:
i. The entrance door requires 10-11 pounds of force to operate. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).
ii. Although an audible alarm is provided, there is no visual alarm. Provide a visual alarm appliance in the toilet room. Standards §§ 4.28.1, 4.28.3.
iii. The air dryer is a protruding object that is not cane-detectable. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.
iv. Toilet Stall for Persons with Disabilities
(1) Women’s Only: The toilet seat is 20-1/4 inches above the finished floor. Provide a toilet with a seat that measures 17 to 19 inches above the finished floor. Standards §§ 4.16.3, 4.17.2, Fig. 30(d).
(2) The coat hook is inaccessible. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(3) Women’s Only: The side grab bar is mounted 37-1/2 inches above the finished floor. Provide grab bars that are mounted between 33 and 36 inches above the finished floor. Standards § 4.17.6, Fig. 30.
h. Ceramics Room: Although it has some features for persons with mobility impairments, the single-user toilet room in the ceramics room is not accessible. To provide program access, provide directional signage directing people to the accessible toilet rooms in the recreation room.
6. By December 31, 2014, the City will complete the following modifications to Tranquility Park Soccer Complex, located at 12222 West Maple Road:
a. Parking: Although 14 of 330 marked spaces are designated as reserved for persons with disabilities, some of the designated spaces are too narrow and the pavement markings of most of them are unclear. On the shortest accessible route to the accessible entrance, provide at least 1 van accessible space and 7 standard spaces designated as reserved for people with disabilities. Ensure that standard accessible spaces are a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional “Van-Accessible” sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
b. Men’s and Women’s Toilet Rooms with Stalls. For each:
i. The toilet room sign is inaccessible. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. Women’s Only: The hot water and drain pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.
iii. The lavatory hardware is inaccessible. Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.5, 4.27.4.
iv. There is no toilet stall provided for persons who use wheelchairs. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
v. Women’s Only: The “alternate” toilet stall has partitions that are 37 inches apart and the toilet paper dispenser is mounted 50 inches from the rear wall. Ensure that the stall is exactly 36 inches wide with a toilet 18 inches from each wall or partition, an outward swinging, self-closing door, and parallel grab bars complying with Fig 30(d). Standards §§ 4.22.4, Fig. 30(d).
c. Drinking Fountain
i. Although a high drinking fountain is provided, there is no lower drinking fountain for persons who use wheelchairs. Provide at least one drinking fountain with a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet; and a spout located at the front of the unit that directs the water flow in a trajectory that is nearly parallel to the front of the unit and is positioned so the flow of water is within 3 inches of the front edge of the fountain and at least 4 inches high. Ensure that fountain controls are operable with one hand, require 5 lbf or less to operate without tight grasping, pinching, or twisting of the wrist; and are front mounted or side mounted near the front edge. Standards §§ 4.15, 4.27.4, Fig. 27.
ii. The drinking fountain is a protruding object that is not cane-detectable. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.
7. By December 31, 2014, the City will complete the following modifications to Columbus Park, located at 1329 S. 24th Street:
a. None of the fixed picnic tables at the park pavilion are accessible to persons who use wheelchairs. Provide at least one picnic table on an accessible route such that there is knee space at the table at least 27 inches high, 30 inches wide, and 19 inches deep, and such that the height of the top of the table is between 28 inches and 34 inches above the ground. Standards §§ 4.32.3, 4.32.4.
b. There is no space on an accessible route near the bleachers that could be used for softball spectators who use wheelchairs. Provide at least 2 wheelchair seating areas, each with a minimum clear ground or floor space of 33 inches wide by 48 inches deep for forward or rear access, or 33 inches wide by 60 inches deep for side access. Ensure that the ground or floor at all wheelchair locations is level, firm, stable, and slip resistant; that wheelchair seating areas are an integral part of the fixed seating plan and are located so as to provide people with physical disabilities a choice of lines of sight comparable to those available for members of the general public; that wheelchair seating areas adjoin an accessible route that also serves as a means of egress in case of emergency; and that at least one fixed companion seat is provided next to each wheelchair seating area. Standards §§ 4.1.3(19)(a), 4.5, 4.33.
8. By December 31, 2014, the City will complete the following modifications to the Johnny Goodman Golf Course, located at 6111 S. 99th Street:
a. Parking
i. Although the parking lot has five standard spaces designated for persons with disabilities, the spaces are narrower than required, there is no van accessible space, the pavement markings are unclear, the surface is not firm, stable, and slip-resistant, and while they are on the shortest route to the golf course, none are provided on the shortest route to the Clubhouse. On the shortest accessible route to the accessible entrance, provide 1 van accessible space and 4 standard spaces designated as reserved for people with disabilities. Ensure that standard accessible spaces are a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional “Van-Accessible” sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
ii. There are no curb cuts adjacent to the parking spaces designated as reserved for persons with disabilities. Provide a curb ramp that is at least 36 inches wide, has a maximum slope of 1:12, is located so that it cannot be obstructed by parked vehicles, and has a stable, firm, and slip-resistant surface with a detectable warning extending the full width and depth of the ramp. If the curb ramp is located where pedestrians must walk across it, provide either flared sides (with a maximum slope of 1:10) or handrails or guardrails to protect against cross traffic. Standards § 4.3.8, 4.7, Fig. 12.
b. Entrance to Clubhouse: The Clubhouse entrance is inaccessible because there is a slope within the door’s required maneuvering clearance.